AC Current transformer TT 100-SD
IPN = 100 A
Split core transducer for the electronic measurement of AC waveform
currents,withgalvanicisolationbetweentheprimarycircuit(power)and
the secondary circuit (measurement).
Electrical data
IPN
IOUT
VSZ
ÎP
Primary nominal current rms
Output current
Output clamping voltage
Overload capability - continuous
- 1 min
100
33.33
7.5
300
4000
At
mA
V
A
A
Features
· Split core type
· Ø 16 mm sensing aperture for non-
contact measurement
· Cable output (1m)
· Isolated plastic case recognized
according to UL 94-V0.
Performance data
X
Overall accuracy @ IPN , TA = 25°C
Linearity error
< ± 1
0.1
60
1.5° ± 1°
50/60
%
%
ppm/K
eG
L
TCIOUT
Dj
Temperature coefficient of IOUT
Phase shift
Advantages
· High accuracy and low phase shift
· High isolation between primary and
secondary circuits
BW
Frequency bandwidth (± 1dB)
Hz
General data
· Compact case
· Cost-effective solution
· Easy installation.
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 25 .. + 70 °C
- 30 .. + 90 °C
100
g
IPxx
Protection degree
IP40
Applications
· Power meters
Isolation characteristics
Current measurement for active
power calculation
Vb
Rated isolation voltage rms1)
with IEC 61010-1 standards and following conditions :
- Reinforced isolation
300
V
· Energy sub-meters
For energy efficiency monitoring,
consumption analysis and costs
allocation
- Over voltage category CAT III
- Pollution degree PD2
- Heterogeneous field
Rms voltage for AC isolation test 2), 50Hz, 1min
Impulse withstand voltage 1.2/50ms
Creepage distance
Clearance distance
Comparative tracking index (Group I)
3.5
6.5
6
6
600
kV
kV
m m
m m
· Power quality monitoring
· Condition monitoring
(e.g. motor loads such as
conveyers, pumps or HVAC)
· Distributed measurement systems
Vd
Vw
dCp
dCl
CTI
1)
2)
Application domain
Notes :
If insulated cable is used for the primary circuit, the voltage category
could be improved according to the primary cable insulation category
(please refer to the cable manufacturer's indications)
· Energy and Automation
between primary (completely filling the hole) and secondary.
Page 1/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
071115/5
www.lem.com