Thermal (T- and TA-Line)
TA45 3 pole Push button
https://www.schurter.com /PG17_20
Circuit Breaker for Equipment thermal, 3 pole, Push button actuation
Basic type
With auxiliary contact
With undervoltage protection
See below:
Approvals and Compliances
Description
Applications
- Thermal circuit breaker
- 2 pole thermal overload protection
- Positively trip-free release
- High configurability
- Power tools
- Industrial appliances
- Power supplies
- Equipment for construction
- Cleaning equipment
- Snap-in or flange mounted
- Quick connect terminal 6.3 x 0.8 mm or screw clamp terminal M3.5 x
6 mm (lineside P1, P2)
References
Weblinks
pdf data sheet, html datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
Rated Voltage AC
Rated current range AC
AC 400 VAC
0.05 - 12 A
Overload
AC: min. 40trips
@ 6 x Ir
Allowable Operation Temp.
Storage Temperature
Vibration Resistance
-10°C to 55°C
-10°C to 55°C
0.ꢀ5 mm @ 10 - 60 Hꢁacc. to IEC
60068-2-6, test Tc10 G @ 60 - 500
Hꢁacc. to IEC 60068-2-6, test Tc
30 G / 18msacc. to IEC 60068-2-2ꢀ,
test Ea
Thermal
Pushbutton
50 - 55g
Conditional short circuit capa- IEC 60934: PC1, AC 400 V: 1kA
city Inc
Short circuit capacity Icn
IEC 60934:
400 VAC: 10x In (max. 3 Zykl.)
front side IP40 acc. to IEC 60529
4kVAC
500VDC > 100 MΩ
mechanical: 50'000switching cycles
AC: 1 x Ir:
Degree of Protection
Dielectric Strength
Insulation Resistance
Lifetime
Shock Resistance
Tripping Type
Actuation Type
Weight
50'000switching cycles
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree-
ments by SCHURTER.
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: TA45
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
VDE Certificate Number: 40019880
UL Approvals
UL
UR File Number: E71572
CCC Approvals
CCC
CCC Certificate Number: 2020970307001847
1