150 Watts
xppower.com
SDS150 Series
•
•
•
•
•
•
•
3” x 5” Footprint
Fits 1U Applications
Convection-cooled
Open Frame & U-Channel Versions
Optional Power Fail Detect Signal
Optional Low Temperature Operation
Up to 90% Efficiency
Specification
Input
General
Input Voltage
Input Frequency
Input Current
• 90-264 VAC (120-370 VDC)
Efficiency
Isolation
• 88ꢀ typical, 90ꢀ max
• 47-63 Hz
• 3000 VAC Input to Output
1500 VAC Input to Ground
500 VDC Output to Ground
• 2.0 A at 115 VAC
1.0 A at 230 VAC
Switching Frequency
Power Density
Signals
• PWM 60 kHz typical, PFC 100 kHz typical
• 6.9 W/In3 for open frame version
• Power Fail Detect = TTL low (option)
• >100 kHrs per MIL-HDBK-217F
Inrush Current
Power Factor
• 20 A at 115 VAC
63 A at 230 VAC
• >0.95
Earth Leakage Current • <0.40 mA at 115 VAC
MTBF
<0.75 mA at 230 VAC
Environmental
Input Protection
• 3.15 A on board fuse
Operating Temperature • 0 °C to +70 °C, derate linearly from 100ꢀ
load at +50 °C to 50ꢀ load at +70 °C,
Output
low temperature option ‘-L’ -40 °C
Output Voltage
• See table
Cooling
• Convection-cooled
• 5-95ꢀ RH, non-condensing
• -40 °C to +85 °C
Output Voltage Trim
Initial Set Accuracy
Minimum Load
•
•
5ꢀ
1ꢀ
Operating Humidity
Storage Temperature
Vibration
• No minimum load required
• 2 s max
• 2 g on 3 axes
Start Up Delay
Start Up Rise Time
Hold Up Time
• 2 ms typical
EMC & Safety
• >16 ms
Emissions
• EN55022, FCC Part 15, level B conducted
• EN61000-3-2
Line Regulation
Load Regulation
Transient Response
• 1ꢀ max, 0.5ꢀ typical
• 5ꢀ max, 3.0ꢀ typical
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
• EN61000-3-3
• 4ꢀ max deviation, recovery to within 1ꢀ
in 500 µs for a 50ꢀ load change
• EN61000-4-2, level 2 Perf Criteria A
• EN61000-4-3, 3 V/m Perf Criteria A
• EN61000-4-4, level 2 Perf Criteria A
• EN61000-4-5, level 3 Perf Criteria A
• EN61000-4-6, level 2 Perf Criteria A
Ripple & Noise
• 1ꢀ pk-pk max
Overvoltage Protection • 112-132ꢀ, recycle input to reset
Overload Protection • 110-150ꢀ with auto recovery
Surge
Conducted Immunity
Dips & Interruptions
Short Circuit Protection • Trip & restart (Hiccup mode),
auto recovery
T
• EN61000-4-11, 70ꢀ U for 10 ms,
Temperature
Coefficient
• 0.04ꢀ/°C
T
T
40ꢀ U for 100 ms, <5ꢀ U for 5000 ms
Perf Criteria A, B, B
Safety Approvals
• EN60950-1, UL60950-1, CSA60950-1
per cUL, CE Mark LVD