MODEL: R7L
CONNECTION DIAGRAMS
■ POWER SUPPLY, LONWORKS TERMINAL ASSIGNMENT
4
5
6
7
NET1 NET2 U (+) V (–)
1
2
3
NET1 NET2 FG
NO.
1
ID
FUNCTION, NOTES
LONWORKS communication 1
LONWORKS communication 2
FG
NET1
NET2
FG
2
3
4
NET1
NET2
U (+)
V (–)
LONWORKS communication 1
LONWORKS communication 2
Power input
5
6
7
Power input
Note: LONWORKS wiring must be paired between NET1 terminals
and/or NET2 terminals.
■ HOST PC CONNECTION
HOST PC
R7L
R7L
LONWORKS
LONWORKS
LONWORKS
Terminator
DATA CONVERSION
■ 0 – 100% DATA CONVERSION
Analog input data is converted into digital representations of 0 – 100% proportional to each scaled range. The converted %
values are expressed in signed 16 bits.
Overrange input is possible from -15 to +115% of the nominal range. When the signal exceeds the limit, the data is xed at
-15% or +115% respectively.
• Input Range 0 – 5V DC
Input Value
Input %
Converted Data, Decimal
≤ -0.75V
0V
5V
-15%
0%
100%
115%
-15.00
0.00
100.00
115.00
≥ 5.75V
115.00
100.00
-0.75
0
-15.00
5.0
5.75
(V)
Analog output is converted in the reverse order of the input data. The output range 0 – 5V DC is expressed as 100.00 at
5.0V (100%) and 0.00 at 0V (0%).
R7L SPECIFICATIONS
ES-7804 Rev.13 Page 4/26