Remote I/O R3 Series MODBUS INTERFACE MODULE

R3-NM1-K3/Q 数据手册

 浏览型号R3-NM1-K3/Q的Datasheet PDF文件第2页浏览型号R3-NM1-K3/Q的Datasheet PDF文件第3页浏览型号R3-NM1-K3/Q的Datasheet PDF文件第4页浏览型号R3-NM1-K3/Q的Datasheet PDF文件第6页浏览型号R3-NM1-K3/Q的Datasheet PDF文件第7页浏览型号R3-NM1-K3/Q的Datasheet PDF文件第8页 
MODEL: R3-NM1  
MODBUS I/O ASSIGNMENT  
ADDRESS  
1 – 1024  
DATA FORMAT NAME  
Digital Output (discrete output)  
Coil (0X)  
1025  
Main / Sub Switching Command (valid only with SW3-3 set to ON)  
Inputs (1X)  
1 – 1024  
Digital Input (discrete input)  
Module Status  
Error Status  
1025 – 1040  
1041 – 1056  
1057 – 1072  
1 – 256  
Data Error Status  
Analog Input  
Input Registers (3X)  
I
257 – 768  
1 – 256  
F
I
Analog Input  
Holding Registers (4X)  
Analog Output  
Analog Output  
257 – 768  
F
I : Integer, 0 – 10000 (0 – 100%)  
F : Floating (32-bit data cannot be accessed using floating addresses.)  
Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation.  
• Module Status indicates whether individual I/O modules are mounted or not. The bit corresponding to the mounted slot turns to  
“1,” and the unmounted slot to “0.”  
• Error Status indicates error status for each module as described below. The bit corresponding to such module turns to “1.”  
R3-TSx, R3-RSx, R3-US4: Input burnout  
R3-DA16A:  
R3-YSx:  
R3-PC16A:  
Power input in error or disconnected  
Output current error (e.g. load unconnected)  
External power supply in error or disconnected  
• Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for each  
module. The bit corresponding to such module turns to “1.”  
• Main / Sub Switching Commands given to the network modules result as follows:  
MAIN’ MODULE  
‘SUB’ MODULE  
OUTPUT MODE  
1
0
1
0
0
1
1
0
Main bus is used; Red light turns on at RUN LED of the I/O modules.  
Sub bus is used; Green light turns on at RUN LED of the I/O modules.  
Main bus is used; Amber light turns on at RUN LED of the I/O modules.  
Output is invalid; RUN LED of the I/O modules turns off.  
TRANSMISSION DATA DESCRIPTIONS  
The DIP SW located at the side of the module species each I/O module’s data allocation (occupied data area).  
For example, when the data areas are assigned as shown below:  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
Module 6  
Module 7  
4
4
4
1
1
1
1
Then the I/O data are assigned as in the table below:  
ADDRESS POSITION  
1 – 4,  
ADDRESS  
1 – 64  
POSITION  
Slot 1  
Input Registers (3X)  
257 – 264  
265 – 272  
273 – 280  
281 – 282  
283 – 284  
285 – 286  
287 – 288  
Slot 1  
Slot 2  
Slot 3  
Slot 4  
Slot 5  
Slot 6  
Slot 7  
Coil (0X)  
Holding Registers (4X)  
Inputs (1X)  
5 – 8,  
9 – 12,  
13,  
65 – 128  
129 – 192  
193 – 208  
209 – 224  
225 – 240  
241 – 256  
Slot 2  
Slot 3  
Slot 4  
14,  
Slot 5  
15,  
Slot 6  
16,  
Slot 7  
For Coil (0X) and Inputs (1X), addresses 16 times assigned data  
areas (Data Allocation Type) are allotted with the Data Allocation  
Type ‘1’ and ‘4. With ‘8’ and ‘16,’ 64 (4 × 16) are automatically al-  
lotted.  
R3-NM1 SPECIFICATIONS  
ES-8354 Rev.24 Page 5/8  
https://www.m-system.co.jp/  

与R3-NM1-K3/Q相关器件

型号 品牌 描述 获取价格 数据表
R3-NM1-L3 MSYSTEM Remote I/O R3 Series MODBUS INTERFACE MODULE

获取价格

R3-NM1-L3/CE MSYSTEM Remote I/O R3 Series MODBUS INTERFACE MODULE

获取价格

R3-NM1-L3/Q MSYSTEM Remote I/O R3 Series MODBUS INTERFACE MODULE

获取价格

R3-NM1-R MSYSTEM Remote I/O R3 Series MODBUS INTERFACE MODULE

获取价格

R3-NM1-R/CE MSYSTEM Remote I/O R3 Series MODBUS INTERFACE MODULE

获取价格

R3-NM1-R/Q MSYSTEM Remote I/O R3 Series MODBUS INTERFACE MODULE

获取价格