MODEL: R3-NCIE1
Remote I/O R3 Series
GENERAL SPECIFICATIONS
Connection
CC-Link IE Field: RJ-45 Modular Jack
NETWORK INTERFACE MODULE
(CC-Link IE Field network)
Internal bus: Via the Installation Base (model: R3-BSx)
Internal power: Via the Installation Base (model: R3-BSx)
RUN contact output: M3 separable screw terminal (torque
0.5 N·m)
27.5 [1.08]
Screw terminal: Nickel-plated steel
Isolation: CC-Link IE Field to internal bus or internal power
to RUN contact output
130
[5.12]
Input error data setting: Input value setting at input module
error with side DIP SW
Dual communication setting: Set with the side DIP switch
Data allocation setting: Set with the side DIP switch
RUN indicator: Green LED ON at normal operating
ERR indicator: Red LED ON at abnormal node
■ RUN CONTACT OUTPUT
109
[4.29]
mm [inch]
MODEL: R3-NCIE1[1]
RUN contact: Turns ON while the green RUN LED is ON (ON
in normal operation).
ORDERING INFORMATION
• Code number: R3-NCIE1[1]
Specify a code from below for [1].
(e.g. R3-NCIE1/CE/W/Q)
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
• Specify the specification for option code /Q
(e.g. /C01)
Mechanical life: 2 × 10 cycles (300 cycles/min.)
7
When driving an inductive load, external contact protection
and noise quenching recommended.
[1] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
CC-Link IE Field COMMUNICATION
Protocol: IEEE 802.3
Mitsubishi PLC Redundant System
blank: Without
Transmission type: 1000BASE-T
/W: With
Communication speed: 1 Gbps
Other Options
Network cable: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
blank: none
/Q: Option other than the above (specify the specification)
Network topology: Line, star and ring
Max. number stations: 120 (Total slave station)
(Number of max. connectable slaves may vary depending
on the master module. Refer to the instruction manual of
the master module)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
Max. station-to-station distance: 100 m
Station type: Remote device station
Link device: RX/RY 128 points, RWw/RWr 64 points
NetWork No.: 1 to 239 (factory default: 1)
/C03: Rubber coating
RELATED PRODUCTS
• PC configurator software (model: R3CON)
Downloadable at M-System’s web site.
For connecting to PC, use commercially available Mini-B
type USB cable. (provided by user)
INSTALLATION
Current consumption: 170 mA max.
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
R3-NCIE1 SPECIFICATIONS
ES-8287 Rev.3 Page 1/8
https://www.m-system.co.jp/