PS-75 Series
75W Single Phase Industrial DIN Rail Power Supply
F eatures :
Univers al A C i nput/F ull range
P rotections :Short circuit/Over load/Over voltage/Over temperature
C ooling by free a ir c onvection
C an be i ns talled on D IN r ail T S -35/7.5 o r 1 5
UL 5 08(indus trial c ontrol e quipment)approved
LE D i ndicator for power on
100% f ull load burn-in tes t
F ix switching frequency a t 50K Hz
3 y ears w arranty
R
SPECIFICATION
MODEL
PS-7512
PS-7524
PS-7548
DC VOLTAGE
12V
24V
48V
RATED CURRENT
CURRENT RANGE
RATED POWER
6.3A
3.2A
1.6A
0 ~ 6.3A
76W
0 ~ 3.2A
0 ~ 1.6A
76.8W
240mVp-p
48 ~ 53V
1.0%
76.8W
RIPPLE & NOISE (max.) Note.2 100mVp-p
VOLTAGE ADJ. RANGE 12 ~ 14V
VOLTAGE TOLERANCE Note.3 2.0%
150mVp-p
OUTPUT
24 ~ 28V
1.0%
LINE R EGULATION
LOAD REGULATION
SETUP, RISE, HOLD TIME
VOLTAGE R ANGE
0.5%
0.5%
0.5%
1.0%
1.0%
1.0%
1000ms, 60ms, 50ms/230VAC
1 800ms, 60ms, 10ms/115VAC at full load
85 ~ 264VAC
47 ~ 63Hz
76%
1 20 ~ 370VDC
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT
80%
81%
INPUT
1.6A / 115V AC 0.96A / 230V AC
INRUSH CURRENT (max.)
LEAKAGE CURRENT
COLD START 20A / 115V AC 40A / 230V AC
<1mA/ 240VAC
105 ~ 150% rated output power
OVER LOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
15 ~ 16.5V 29 ~ 34V 58 ~ 65V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
85 (TSW1) Detect on heat sink of power transistor
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
5
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-10 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-20 ~ +85 , 10 ~ 95% RH
ENVIRONMENT
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
UL508, EN60950Approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
SAFETY &
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMC
(Note 4)
Compliance to EN55011,EN55022 (CISPR22) Class B
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,61,8, ,E1NV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, cAriteria
123.1K hrs min. MIL-HDBK-217F (25
55.5*125.2*100mm (W*H*D)
0.6Kg; 20pcs/13Kg/1.1CUFT
)
OTHERS
NOTE
DIMENSION
PACKING
1. A ll parameters N OT s pecially mentioned are measured at 230VAC i nput, rated load and 25 of ambient temperature.
2. R ipple & n oise a re measured at 20MHz of bandwidth by using a 1 2" twisted pair-wire terminated with a 0 .1uf & 4 7uf parallel capacitor.
3. T olerance : i ncludes s et up tolerance, line regulation and load regulation.
4. T he power s upply is c onsidered a c omponent which will be installed into a f inal equipment. T he final equipment must be re-confirmed that it still meets
E MC d irectives.
35 Royal Road, Flemington, NJ 08822-6000 • (tel.) 908-806-9400 • (fax) 908-806-9490 • www.altechcorp.com