Modular High Power-D-Box
Description
The Power-D-Box® is a compact 2U power distribution system made
of aluminium in an enclosure with anodised front plate. Protection of
the loads is by means of hydraulic-magnetic circuit breakers.
Ordering information
PDB Standard Power-D-Box® 19“ with interchangeable ETSI flange - 19“
Protected pole
N
negative pole protected
Module
D
X8345-D01*
xx Number of ways (total)
Main terminals
®
High Power-D-Box
R
on the rear
Load terminals
R on the rear
Technical data
F
on the front
PDB
-
N - D 08 - R F ordering example
19“ Power-D-Box®
length
height
84 modules (426.72 mm)
2 U (88.90 mm)
*technical data on www.e-t-a.de
material: aluminium
Plug-in type circuit breakers 8345-.01A-W0..-DB1B2B-..
Preferred types
with and without auxiliary contact module
X8345-S01KW102-M
High Power-D-Box®:
Rated voltage
DC 48 V, DC 65 V, DC 80 V
(other voltage ratings upon request)
PDB - N - D 06 - RF: load current max. 65 A with 2 x 3 ways
PDB - N - D 06 - RR: load current max. 125 A with 2 x 3 ways
PDB - N - D 08 - RF: load current max. 65 A with 2 x 4 ways
PDB - N - D 08 - RR: load current max. 125 A with 2 x 4 ways
PDB - N - D 10 - RF: load current max. 65 A with 2 x 5 ways
PDB - N - D 10 - RR: load current max. 85 A with 2 x 5 ways
PDB - N - D 12 - RF: load current max. 65 A with 2 x 6 ways
PDB - N - D 12 - RR: load current max. 85 A with 2 x 6 ways
PDB - N - D 16 - RR: load current max. 6 x 85 A + 10 x 30 A
with 2 x 8 ways
Load
125 A per plug-in unit (when using
circuit breakers rated 80 A plus,
total load of the neighbouring
slots must not exceed 160 A)
Total current per supply
232 A total current at
ambient temperature -30...60 °C
(-22 °F...140 °F)
UL/CSA: 230 A total current at
ambient temperature -30...+50 °C
Features
Fire resistance
(IEC 60695, part 2-2)
self-extinguishing
l
Plug-in type circuit breakers, 8345-.01.-W0, extendable in
service, with or without auxiliary contact, load per way
0.1…125 A
Terminal design*
Supply feed
35...95 mm2, flexible,
screw-type terminal 25...95 mm2
with wire end ferrule
l
l
l
l
Extremely compact design (installation depth 310 mm)
Standard redundant design (2 x 3, 2 x 4, 2 x 6)
Group signalling for redundant line entry A and/or B is standard
To be used with industrially manufactured power distribution
modules (X8345-D01), protected against brush contact
Labelling strips for individual marking
Loads
1.5...35 mm2, flexible,
screw-type terminal 1.5...35 mm2
with wire end ferrule
Signalling
Ground
screw-type terminal 1.5 mm2
bolt (M8)
l
l
l
l
Blank covers (bulk shipped)
Weight
approx. 7.5 Kg
isolated cable clamp rail (X 223 260 01) optional as accessory
Integral jumper ground to plus pole (freely configurable by the
customer as an option)
Conformity
CE to EN60950-1
*(detailed values on page 4)
6
l
Other versions are available upon request (e.g. with series fuse,
separate circuits, non-redundant circuits, customer-specific
marking, protected plus pole etc.)
Approvals
Authority
Standard
Rated voltage
Current ratings
UL
UL60950-1
max. DC 80 V
max. 125 A*
per channel
CSA
C22.2 No
60950-1-07
max. DC 80 V
max. 125 A*
per channel
* depending on type, see preferred types
max. total current of neighbouring channels 160A