SpectrAlert Advance Specifications
Architect/Engineer Specifications
The horn/strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service.
The horn/strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated
lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three-pattern and a non-temporal (continuous)
pattern. These options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on
horn/strobe models shall operate on a coded or non-coded power supply.
Outdoor Products
SpectrAlert Advance outdoor horn/strobe shall be listed for outdoor use by UL and shall operate between minus 40 degrees and 151 degrees Fahrenheit. The
products shall be listed for use with a System Sensor outdoor/weatherproof back box with half inch and three-fourths inch conduit entries.
Physical/Electrical Specifications
Operating Temperature
Strobe Flash Rate
–40°F to 151°F (–40°C to 66°C)
1 flash per second
Nominal Voltage
Regulated 120VAC
Operating Voltage Range
Input terminal wire gauge
Dimensions
96 – 132VAC
12 to 18 AWG
5.7˝L × 5.1˝W × 2.0˝D (145 mm L × 130 mm W × 51 mm D)
Candela Derating
For K series products used at low temperatures, listed candela ratings must be
reduced in accordance with this table.
Strobe Output (cd)
Listed Candela
Candela rating at –40°F
135
150
177
185
135
150
177
185
P2RHK-120 Dimensions
P2RHK-120 Mounting
4.7˝
2.5˝
120V WIRES
120V MOUNTING PLATE MP120K
2.0˝
5.6˝
5.7˝
Wall-mount horn/strobes
5.1˝
Wall weatherproof back box
SpectrAlert Advance Ordering Information
Model
Description
2-wire Horn/Strobe, High cd, Red, Outdoor, 120VAC
P2RHK-120*
Notes:
*Includes P2RHK 2-wire horn/strobe, MP120K 120VAC adapter mounting plate, and weatherproof back box.
“High cd,”refers to strobes that include 135, 150, 177, and 185 candela settings.
All outdoor units ending in“K”include a weatherproof back box.
©2006 System Sensor.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0413-000 • 12/06 • #0000