MB13-SERIES
Three Phase Input Noise Filter with Block Terminal
Ⅵ Features
(1)Block Terminal with Cover
Simple wire connection by block terminal.
High safety by terminal cover.
(2)Three Phase Power Line Filter
Available for Star connection : 400Vac line-line
Available for Delta connection : 200Vac line-line
(3)High Attenuation in Compact Package
Ⅵ Safety standard
UL1283,
CSA Std. C22. 2 No. 8
EN133200 (New European Standard)
Ⅵ Specifications
MODEL
MB1310
MB1320
20A
MB1330
MB1340
40A
MB1350
50A
ITEMS
1
2
3
4
5
Rated Voltage (AC)
Rated Current (AC) (Note 1)
Test Voltage
Isolation Resistance
Leakage Current 250V 60Hz
500V 60Hz
500V(50/60Hz)
30A
10A
2500VAC(20mA) Terminal to case, 1min. at 25˚C , 70%RH
100MΩ min. Terminal to case, 500VDC at 25˚C, 70%RH
1.0mA max.
2.0mA max.
6
7
8
9
DC Resistance
80m Ω max.
30m Ω max.
20m Ω max.
35˚C max.
–25˚C~+85˚C
11m Ω max.
7m Ω max.
Temperature Rise
Operating Temperature
Operating Humidity
30%~95% RH (No Dewdrop)
–40˚C~+85˚C
10%~95% RH (No Dewdrop)
10 Storage Temperature
11 Storage Humidity
12 Vibration
13 Safety Standard
14 Weight (typ)
10~55~10Hz,Amplitude (Sweep for 1min) 1.5mm(9G max.) X,Y,Z 2 hours each
Bilt to meet : UL1283,CSA C22.2 No.8, EN133200
1800g
1800g
1800g
2800g
2800g
15 MTBF(hours) (Note 2)
<
573,000
480,000
521,000
421,000
395,000
(Note1): Value for Ta 50°C. For Ta>50°C derate according to the derating curve shown below.
=
(Note2): Calculated based on the part stress analysis prediction method as specified in MIL-HDBK-217F.
ⅥDERATING
ⅥCIRCUIT
ⅥAPPLICATIONS
Star connection
Delta Connection
3 Phase 4 Wires 400V line-line. Unused Neutral line
3 Phase 3 Wires 200V line-line
noise
filter
noise
filter
noise
filter
noise
filter
Note: For inverter application
Do not use MB series between
inverter and motor.
motor
Inverter
141