Current Transducer LTS 25-NP
IPN = 25 At
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
16054
Electrical data
IPN
IPM
VOUT
Primary nominal current rms
Primary current, measuring range
Output voltage (Analog) @ IP
IP = 0
Sensitivity
Number of secondary turns (± 0.1 %)
Load resistance
25
0 .. ± 80
2.5 ± (0.625·IP/IPN)V
2.5 1)
25
At
At
Features
· Closed loop (compensated) multi-
range current transducer using the
Hall effect
· Unipolar voltage supply
· Isolated plastic case recognized
according to UL 94-V0
· Compact design for PCB mounting
· Incorporated measuring resistance
· Extended measuring range.
V
mV/A
G
NS
RL
RIM
2000
³ 2
50
< 50
5
kW
W
ppm/K
V
Internal measuring resistance (± 0.5 %)
TCRIM Temperature coefficient of R IM
VC
IC
Supply voltage (± 5 %)
Current consumption @ VC = 5 V
Typ
28+IS2)+(VOUT/RL)mA
Advantages
Accuracy - Dynamic performance data
· Excellent accuracy
· Very good linearity
X
Accuracy @ IPN , TA = 25°C
Accuracy with RIM @ IPN , TA = 25°C
Linearity error
± 0.2
± 0.7
< 0.1
%
%
%
· Very low temperature drift
· Optimized response time
· Wide frequency bandwidth
· No insertion losses
· High immunity to external
interference
e
L
Typ Maxi
TCVOUT Temperature coefficient of VOUT @ IP = 0 - 10°C .. + 8 5°C 50
100 ppm/K
150 ppm/K
50 3) ppm/K
- 40°C .. - 10°C
- 40°C .. + 85°C
TCG
VOM
Temperature coefficient of G
Magnetic offset voltage@ IP = 0,
· Current overload capability.
after an overload of 3 x IPN
± 0.5
± 2.0
± 2.0
mV
mV
mV
5 x IPN
10 x IPN
Applications
· AC variable speed drives and servo
motor drives
tra
tr
Reaction time @ 10 % of IPN
Response time to 90 % of IPN step
< 100
< 400
ns
ns
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies (UPS)
· Switched Mode Power Supplies (SMPS)
· Power supplies for welding
applications.
di/dt di/dt accurately followed
> 60
DC .. 100
DC .. 200
A/µs
kHz
kHz
BW
Frequency bandwidth (0 .. - 0.5 dB)
(- 0.5 .. 1 dB)
General data
TA
TS
Ambient operating temperature
Ambient storage temperature
Insulating material group
Mass
- 40 .. + 85
- 40 .. + 100
III a
°C
°C
Applicationdomain
m
10
g
4)
Standards
EN 50178: 1997
IEC 60950-1: 2001
· Industrial.
1)
Notes:
Absolute value @ TA = 25°C, 2.475 < VOUT < 2.525
IS= IP/N S
Only due to TCRIM
Specification according to IEC 61000-4-3 are not guaranteed between
180 and 220 MHz.
2)
3)
4)
Copyright protected.
Page 1/3
070129/19
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com