With compatible analog sensors and addressable input and
control interface devices, and its remote status and control
capabilities, the IF602VE provides system engineers with
all the tools necessary to design effective system solutions
for any application.
Ordering Information
Model
Description
IF602VE-126 IF602 analog addressable system, con-
sisting of the following:
•
•
•
IF602 common control.
The IF602VE can also control bulk fire-suppressant materi-
als releasing. The IF602VE is capable of releasing the fol-
lowing NFPA types of suppressant: 13 Sprinkler, 15 Water
Spray, 11 Low-Expansion Foam, 16 Water Foam, 17 Dry
Chemical, and 2001 Clean Agent.
8.0 amp main power supply.
One (1) analog circuit module
(126 analog addressable points).
Basic audio subsystem with one 25W
amplifier and microphone.
•
Architectural/Engineering Specifications
Cabinet:
30.0" H x 22.0" W x 5.5" D
The control panel furnished and installed shall be capable
of supporting 252 addressable devices and two analog
loops. The panel shall utilize a fully digital Signaling Line
Circuit (SLC) protocol. The panel shall contain four on-
board Notification Appliance Circuits (NACs) that support
multiple synchronization protocols. The panel shall utilize a
160-character Liquid Crystal Display (LCD) and a 1,000-
event history log. The panel shall be a Gamewell-FCI
IF602VE.
(72.2 H x 55.88 W x 13.97 D cm)
IF602VE-252 IF602 analog addressable system, con-
sisting of the following:
•
•
•
IF602 common control.
8.0 amp main power supply.
Two (2) analog circuits module
(252 analog/addressable points).
Basic audio subsystem with one 25W
amplifier and microphone.
•
Specifications
Cabinet:
30.0" H x 22.0" W x 5.5" D
(76.2 H x 55.88 W x 13.97 D cm)
Common Control:
Standby Current:
Alarm Current:
0.125A
IF602VE-126Z IF602 analog addressable system, con-
sisting of the following:
0.171A plus signaling circuit power,
plus 0.002A for master box, or plus
0.022A for reverse-polarity.
120 VAC, 3.0A; or 240 VAC, 1.5A
•
•
•
IF602 common control.
8.0 amp main power supply.
One (1) analog circuit module
(126 analog addressable points).
Basic audio subsystem with 8-zone
integrated audio circuit splitter.
One 25W amplifier and microphone.
Input Power:
Auxiliary Output:
S+/S–, A+/A–:
•
•
2.0A maximum
Common Relays:
1.0A @ 30 VDC or 0.5A VAC @ 250
Cabinet:
30.0" H x 22.0" W x 5.5" D
(76.2 H x 55.88 W x 13.97 D cm)
Notification Appliance Circuits:
Circuits:
Output:
Four Class B, two Class A.
3.0A maximum@24 VDC per circuit.
Maximum 8.0A total for all circuits.
IF602VE-252Z • IF602 analog addressable system,
consisting of the following:
Analog SLC:
126
252
0.055A
0.055A
•
•
•
IF602 common control.
Standby Current:
Alarm Current:
0.045A
0.045A
8.0 amp main power supply.
Two (2) analog circuits module
(252 analog addressable points).
Basic audio subsystem with one 25W
amplifier and microphone.
Panel Dimensions:
VE Cabinet:
30.0" H x 22.0" W x 5.5" D
•
(76.2 H x 55.88 W x 13.97 D cm)
Battery Storage Dimensions
(without zone splitter):
Cabinet:
30.0" H x 22.0" W x 5.5" D
VE Cabinet:
8.0" H x 22.0" W x 5.5" D
(20.32 H x 55.88 W x 13.97 D cm)
(76.2 H x 55.88 W x 13.97 D cm)
IdentiFlex 602VE and Audio Subsystem
Installation/Operating Manual
CTM-602, city-tie/remote signaling
module, for 602 Series panels.
ISO-232, RS-232 serial-port isolator
module, for 602 Series panels.
52286
30177
31078
Relative Humidity: 93% non-condensing
Temperature
Rating:
32°F – 120°F (0°C – 49°C)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2497 Rev. A page 3 of 4