MODEL: HVPN
Space-saving Plug-in Signal Conditioners H-UNIT
RELATED PRODUCTS
Mounting Block is required. See the data sheet for model
MB.
LOOP POWERED I/P TRANSDUCER
Functions & Features
• Code number of the Mounting Block (e.g. MB-08)
• Converting a DC input into a proportional standard
pneumatic signal
GENERAL SPECIFICATIONS
Construction: Plug-in
• Loop powered
• Semiconductor pressure sensor in the feedback circuit
• High resolution
Connection
Input: M3.5 screw terminals (torque 0.8 N·m)
Pneumatic: Rc 1/4" or 1/4" NPT female;
(torque ≤ 12 N·m)
• No mounting position effect
• Highdensity mounting
Material
Typical Applications
• Housing: Flame-resistant resin (black)
• Base socket: Die cast aluminium
• Valve section: Die cast aluminium
• Screw terminals: Nickel-plated steel;
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
• Converting a 4 – 20 mA from a PID controller into a
pneumatic signal
25 (.98)
H•UNIT
HVP
150
(5.91)
INPUT SPECIFICATIONS
Equivalent input impedance: Approx. 310 Ω at 20 mA
The voltage measure at the input terminals changes
corresponding to the input signal as in the diagram below.
Be sure that the device at the input side allows the load
increase.
120
(4.72)
mm (inch)
approx. 6.2
MODEL: HVPN–[1]A[2]
6.0
ORDERING INFORMATION
• Code number: HVPN-[1]A[2]
5.8
Specify a code from below for each of [1] and [2].
(e.g. HVPN-2A2S)
approx. 5.7
4
12
20
INPUT CURRENT [mA]
[1] PNEUMATIC CONNECTION
2: Rc 1/4"
OUTPUT SPECIFICATIONS
■ Output:
7: 1/4" NPT fitting
19.6 – 98.1 kPa, 0.2 – 1.0 kgf/cm
2
20 – 100 kPa, 0.2 – 1.0 bar
INPUT
Current
20.7 – 103.4 kPa, 3 – 15 psig
The output goes below 0 % if the input loop is open.
Maximum air delivery: 60 Nl/minute (2.1 SCFM)
Maximum air exhaust: 60 Nl/minute (2.1 SCFM)
A: 4 – 20 mA DC
[2] OUTPUT
1S: 19.6 – 98.1 kPa
2S: 20 – 100 kPa
INSTALLATION
Supply pressure: 140 kPa (1.4 kgf/cm , 1.4 bar, 20 psig)
2
3S: 20.7 – 103.4 kPa
±10 %. Use dry air containing no carbon black or other
foreign particles. To ensure reliability use an air filter (0.01
microns).
1: 0.2 – 1.0 kgf/cm
2: 0.2 – 1.0 bar
3: 3 – 15 psig
2
Air consumption: 6 Nl/minute (0.21 SCFM)
HVPN SPECIFICATIONS
ES-3440 Rev.15 Page 1/3
https://www.m-system.co.jp/