MODEL: HVP
/A3S: 20.7 – 103.4 kPa
/A2: 0.2 – 1.0 bar
Space-saving Plug-in Signal Conditioners H-UNIT
/A3: 3 – 15 psig
I/P TRANSDUCER
Functions & Features
Pneumatic Connection
blank: Rc 1/4"
• Converting a DC input into a proportional standard
pneumatic signal
/P7: 1/4" NPT fitting
• Semiconductor pressure sensor in the feedback circuit
• High resolution
RELATED PRODUCTS
Mounting Block is required. See the data sheet for model
• No mounting position effect
• High-density mounting
MB.
• Code number of the Mounting Block (e.g. MB-08)
Typical Applications
• Converting a 4 – 20 mA from a PID controller into a
pneumatic signal
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
25 (.98)
Input & power input: M3.5 screw terminals (torque 0.8
N·m)
H•UNIT
HVP
Pneumatic: Rc 1/4" or 1/4" NPT female; (torque ≤ 12 N·m)
Material
150
(5.91)
•Housing: Flame-resistant resin (black)
•Base socket: Die cast aluminium
•Valve section: Die cast aluminium
•Screw terminals: Nickel-plated steel;
Isolation: Input to power
120
(4.72)
mm (inch)
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
MODEL: HVP–[1]–R[2]
INPUT SPECIFICATIONS
■ DC Current:
ORDERING INFORMATION
• Code number: HVP-[1]-R[2]
Shunt resistor attached to the input terminals (0.5 W)
Specify a code from below for each of [1] and [2].
(e.g. HVP-6-R/A2S/P7)
OUTPUT SPECIFICATIONS
■ Output:
19.6 – 98.1 kPa, 0.2 – 1.0 kgf/cm
2
[1] INPUT
Current
20 – 100 kPa, 0.2 – 1.0 bar
20.7 – 103.4 kPa, 3 – 15 psig
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
The output goes below 0 % if the input loop is open.
Maximum air delivery: 60 Nl/minute (2.1 SCFM)
Maximum air exhaust: 60 Nl/minute (2.1 SCFM)
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
POWER INPUT
DC Power
INSTALLATION
Supply pressure: 140 kPa (1.4 kgf/cm , 1.4 bar, 20 psig)
2
R: 24 V DC
±10 %. Use dry air containing no carbon black or other
foreign particles. To ensure reliability use an air filter (0.01
microns).
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS (multiple selections)
Output
Air consumption: 6 Nl/minute (0.21 SCFM)
Current consumption: Approx. 30 mA
blank: 0.2 – 1.0 kgf/cm
/A1S: 19.6 – 98.1 kPa
/A2S: 20 – 100 kPa
2
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface; Standard Rack Mounting Frame (BX-
HVP SPECIFICATIONS
ES-3421 Rev.13 Page 1/3
http://www.m-system.co.jp/