G3J-T-C
Specifications
■ Certified Standards
UL 508, CSA 22.2 No. 14
■ Ratings (at an Ambient Temperature of 25°C)
Power Supply
Item
Operating input power
supply specifications
AC Model
DC Model
Rated power supply voltage
Operating voltage range
Current consumption
100 to 240 VAC
85 to 264 VAC
40 mA max. (at 100 to 240 VAC) 70 mA max. (at 12 to 24 VDC)
12 to 24 VDC
10.2 to 26.4 VDC
Operating (Input) Circuit
AC Model
DC Model
Input
method voltage terminals 3 and 2
input
No-
Short-circuiting/opening terminals 3 and 1 or
Input current
10 mA max. (at 12 to 24 VDC)
Short-circuiting/opening terminals 3 and 1 or
method voltage terminals 3 and 2
Input
No-
SSR input short-circuited: Maximum
impedance of 1 kΩ,
Maximum residual
voltage of 1 V
input
SSR input turned ON: Maximum residual
voltage of 2 V between
short-circuited
SSR input open:
Relay input:
Minimum
impedance of
100 kΩ
terminals
SSR input turned OFF:Maximum leakage
current of 0.15 mA
For minute signals
Relay input:
For minute signals
Main Circuit (for Both AC and DC Models)
Item
Model
G3J-T217BL-C
200 to 240 VAC
G3J-T211BL-C
G3J-T205BL-C
Rated load voltage
Rated voltage range
180 to 264 VAC
17.4 A (at 40°C)
0.5 A
Rated carry current (See note 1.)
Minimum load current
Inrush current resistance (peak value)
Overload resistance
11.1 A (at 40°C)
350 A (60 Hz, 1 cycle)
4.8 A (at 40°C)
500 A (60 Hz, 1 cycle)
150 A (60 Hz, 1 cycle)
Refer to Engineering Data on page 5
Closed current (effective value)
AC3
AC4
174 A
111 A
48 A
208.8 A
139.2 A
174 A
133.2 A
57.6 A
Breaking current (effective value) AC3
AC4
88.8 A
38.4 A
111 A
48 A
Applicable 3-phase inductive motor (See note 2.) 200 to 220 VAC
200 to 220 VAC
2.2 kW (11.1 A)
200 to 240 VAC
11.1 A
200 to 220 VAC
0.75 kW (4.8 A)
200 to 240 VAC
4.8 A
load
(AC3, AC4, AC53-a)
3.7 kW (17.4 A)
200 to 240 VAC
17.4 A
Resistive load (AC1) (See note 3.)
Note: 1. The rated carry load depends on the ambient temperature. For details, refer to the Load Current vs. Ambient Temperature graph in
Engineering Data.
2. Satisfies switching test conditions of AC3, AC4, and AC53-a. (Refer to Engineering Data on page 5 for the test conditions.)
3. Single-phase loads cannot be used.
Monitor Output
Note: Internal wiring
Item
Operating input power AC model (See note.)
supply specifications
DC model (See note.)
5
5 (+)
Rated power supply voltage
Operating voltage range
Rated carry current
100 to 240 VAC
85 to 264 VAC
50 mA
12 to 24 VDC
10.2 to 26.4 VDC
0.2 A
6
6 (−)
AC model
DC model
Minimum load current
3 mA
3 mA
2