G3J-S
■ Characteristics
Item
G3J-S405BL
G3J-S403BL
G3J-S211BL
G3J-S205BL
Ramp-up time
Set within a range from 1 to 25 s.
Reset time
5/6 cycles of load power supply + 1 ms max.
Set within a range from 200% to 450% In.
1.8 VRMS max.
Starting torque
Output ON-voltage drop
Leakage current
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
1.6 VRMS max.
10 mA max. (at 200 VAC)
20 mA max. (at 400 VAC)
100 MΩ min. (at 500 VDC)
2,500 VAC, 50/60 Hz for 1 min
Destruction: 10 to 55 to 10 Hz, 0.75–mm single amplitude
Destruction: 294 m/s2
Operating: –20°C to 60°C (with no icing or condensation)
Storage: –30°C to 70°C (with no icing or condensation)
Ambient humidity
Weight
Operating: 45% to 85%
730 g max.
Certified standards
UL508 File No. E64562
CSA 22.2 No. 14 File No. LR35535
IEC947-4-1 File No. 96.2597.02
EMC
Emission AC mains
Emission Electromagnetic
Immunity ESD
IEC947-4-2, CISPR 11 Class A
IEC947-4-2, CISPR 11 Class A
IEC947-4-2, IEC801-2:
4 kV contact discharge
8 kV air discharge
Immunity Electromagnetic
Immunity EFT
IEC947-4-2, IEC1000-4-3
10 V/m (80 MHz to 1 GHz)
IEC947-4-2, IEC801-4:
2 kV AC power-signal line
IEC947-4-2, IEC1000-4-5
1 kV differential mode
Immunity Surge transient
2 kV common mode
IEC947-4-2, IEC/DIS1000-4-6
10 V (0.15 to 80 MHz)
Immunity RF disturbance
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
3