Chassis Mount Filters ꢀ Motor Drive Filters
FLLD series
AD type
Three phase and neutral ꢀ general performance
This three phase and neutral filter series provides a good
level of attenuation across a broad frequency spectrum.
The filter housing`s small footprint and lowꢀprofile
ensures ease of installation within manufactures original
equipment.
The AD series is particularly suited for UPS, switch mode
power supplies, industrial control systems and other such
applications.
• Current ratings from 16A to 25A
• High symmetric and asymentric attenuation
• Screw or fastꢀon termination
• Lowꢀprofile and compact enclosure
Electrical Specifications
• Captive nut mounting
Rated voltage (VR): max 440V (phꢀph), 50/60Hz
Rated current (IR): referred to room temperature = 40°C
Leakage current (IL): at VR / √ 3, 50Hz, max value
Voltage test (2 s.): line to ground 2700Vdc
line to line 1700Vdc
Mechanical Specifications
Manufacture:
metal case; captive nut M5 for
mounting, electrical components sealed
with selfꢀextinguishing resin.
Climatic category:
HPF (25/085/21);
Connections:
faston 6.3 x 0.8mm (16A),
Temperature range: ꢀ25°C to +85°C
threaded bar with metric nut M4 (25A).
Filter Range
FLLD3 series
AD type
IR
L1
Cx1
Cx2
Cy1
Cy2
IL
R
R
(A)
(ꢁF)
(ꢁF)
(pF)
(pF)
(mA) (M ꢂ)
(M ꢂ)
(mH)
Code
FLLD3016AAD01 16 4 x 1.8 3 x 1 3 x 1 15000
FLLD3025AAD01 25 4 x 1.1 3 x 1 3 x 1 15000
15000 <3.2 3 x 0.33 0.62
15000 <3.2 3 x 0.33 0.62
* other variants on request
Insertion loss (typical): Asymmetrical (line to ground)
...16AAD01
ꢀꢀꢀ ...025AAD01
Insertion loss (typical): Asymmetrical (line to ground)
...16AAD01
ꢀꢀꢀ ...025AAD01
Approvals
Made in accordance to VDE, UL and CSA requirements
11/2009
3