MODEL: F2PP
Super-mini Signal Conditioners F2 Series
[3] OUTPUT LOGIC
N: The same as the input
R: Inverted
PULSE ISOLATOR
Functions & Features
• Galvanically isolating pulse rate signals
• Input frequency = output frequency
• Various outputs (open collector and voltage pulses)
• High-density mounting
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Typical Applications
[4] OPTIONS
blank: none
• Isolating field pulse signals in order to reduce noises
• Changing e.g. dry contact signal to e.g. 5 V signals
/Q: With options (specify the specification)
22.5 (.89)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
75
(2.95)
/C02: Polyurethane coating
GENERAL SPECIFICATIONS
Construction: Stand-alone; terminal access at the front
107
(4.21)
mm (inch)
Connection: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm , stripped length 7 mm)
2
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
MODEL: F2PP–[1][2][3]–R[4]
Frequency range: Input and output are the same.
Chattering protection: Filter provided for mechanical
contact input
ORDERING INFORMATION
• Code number: F2PP-[1][2][3]-R[4]
Specify a code from below for each of [1] through [4].
(e.g. F2PP-33N-R/Q)
Input pulse sensing: DC coupled
• Frequency range (e.g. 0 – 1000 Hz)
• Specify the specification for option code /Q
(e.g. /C01)
INPUT SPECIFICATIONS
Excitation: 12 V DC @30 mA; shortcircuit protection
■ Open Collector
Sensing: Approx. 12 V DC @ 3 mA
ON/OFF level: ≤ 200 Ω / 0.6V for ON, ≥ 100 kΩ / 6V for OFF
Low frequency open collector output
Maximum frequency: 30 Hz
[1] INPUT
1: Mechanical contact (max. 30 Hz)
2: Open collector (max. 10 kHz)
3: Voltage pulse (max. 10 kHz)
Pulse width time requirement: 10 msec. min. for ON and
OFF
Note: When the output signal is Low frequency open
collector, the max. input frequency is 30 Hz.
High frequency open collector output
Maximum frequency: 10 kHz
Pulse width time requirement: 10 μsec. min. for ON and OFF
■ Mechanical Contact
[2] OUTPUT
1: Low frequency open collector (max. 30 Hz)
2: High frequency open collector (max. 10 kHz)
3: 5 V pulse (max. 10 kHz)
Maximum frequency: 30 Hz
Pulse width time requirement: 10 msec. min. for ON and
OFF
4: 12 V pulse (max. 10 kHz)
Sensing: Approx. 12 V DC @3 mA
ON/OFF level: ≤ 200 Ω / 0.6 V for ON, ≥ 100 kΩ / 6 V for OFF
■ Voltage Pulse: Square or sine waveforms
Low frequency open collector output
Maximum frequency: 30 Hz
5: 24 V pulse (max. 10 kHz)
F2PP SPECIFICATIONS
ES-5438 Rev.6 Page 1/3
http://www.m-system.co.jp/