IPN = 100..1000 A
AC/DC Current transducer DHR-C10
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement). True RMS 0-10V
voltageoutput.
Features
Electrical data
PrimaryNominal
DC & AC Current
IPN (A.t.RMS)
Primary AC Current
Max. Peak Value
IP (A) (*)
Output voltage
(Analog)
VOUT (VDC)
Type
· VFD and SCR waveforms current
measurement
· True RMS output
100
200
300
400
500
600
1000
600
600
0-10
0-10
0-10
0-10
0-10
0-10
0-10
DHR 100 C10
DHR 200 C10
DHR 300 C10
DHR 400 C10
DHR 500 C10
DHR 600 C10
DHR 1000 C10
· Panel mounting
· Eliminates insertion loss
· Insulated plastic case recognized
according to UL94-V0
1000
1000
1800
1800
1800
Advantages
RL
VC
IC
VSL
ÎP
Load resistance
Supply voltage
Current Consumption
Output voltage limitation (0-10V)
Overload capability (Ampere Turns)
³ 10
+ 20 .. 50 V DC
30
< 14
30000
kW
· Large aperture for cable up to
Ø32mm
mA
V
A.t
· High isolation between primary and
secondary circuits
· Easy installation
Performance data
X
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (1% of IPN .. ± IPN)
Electrical offset voltage, TA = 25°C
Temperature coefficient of VOE ( 0..+60 °C)
(-40..+70 °C)
Temperature coefficient of VOUT (% of reading)
Response time tp 90% of IPN step
Frequency bandwidth (±1dB)
< ± 1 % of IPN
< ± 1.0 % of IPN
< ± 1.0 % of IPN
Applications
e
L
VOE
· VFD Controlled Loads
TCVOE
± 2.0
± 4.0
± 0.1
< 150
mV/K
mV/K
%/K
VFD output indicates how the motor
and attached load are operating.
· SCR Controlled Loads
TCVOUT
tr
BW
m s
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
DC 20..6000Hz
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 40 .. + 70 °C
- 40 .. + 85 °C
260
g
IPxx
Protection degree
IP20
· Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Note : (*) The Max. Peak AC Current is the highest peak level of the primary signal that is
taken into account for accurate True RMS calculation. Yet the device is designed for
maximum continuous True RMS value equal to IPN, whereas the output is limited by
the above specified output limitation.
Application domain
· Energy and Automation
Page 1/3