C o m p o n e n t P o w e r AC Fro n t En d M o d u le s
5 0 0 & 1 0 0 0 Wa tts
TH E XP ERTS IN P O W ER
C P H S e rie s
8 5 -2 6 4 VAC In p u t
•
•
P FC to EN6 1 0 0 0 -3 -2
•
Effic ie n c y u p to 9 5 %
•
Fixe d S w itc h in g Fre q u e n c y
•
Pa ra lle l O p e ra tio n
•
C o m p a tib le w ith C P M S e rie s
•
In te rn a tio n a l Ap p ro va ls
S p e c ific a tio n
In p u t
Switching Frequency
Power Good Signal
•
•
170 kHz CPH500, 130 kHz CPH1000
Open-collector output, max sink
current 5 mA, max voltage 35 V
CPH500
Input Voltage
•
85-264 VAC (derate the CPH1000 to
850 W between 85 & 95 VAC)
Input Frequency
•
•
47-63 Hz
Inverter Operation
Monitoring
•
•
Open-collector output, max sink
current 5/10 mA for CPH500/CPH1000
Input Current
(Typical)
5.6/4.0 A at 115/230 VAC CPH500
11.5/8.5 A at 115/230 VAC CPH1000
Enable Signal
Open-collector output, max sink
current 10 mA, max voltage 35 V
CPH1000 only
Inrush Current
•
15/30 A typ at 115/230 AC CPH500
CPH1000 limited by external
resistance
contact technical sales for details
En viro n m e n ta l
Inrush Current
Protection
•
•
•
Standard
Operating
•
-20 °C to +85 °C (aluminium baseplate)
Temperature
Power Factor
0.98 typical (complies with
EN61000-3-2 85-255 VAC)
Storage Temperature
Humidity
•
-40 °C to +85 °C
•
•
20-95% RH non-condensing
Leakage Current
<0.3 mA CPH500, <0.75 mA CPH1000
Vibration
10-55 Hz 5G 3 minute period,
60 mins along each X, Y & Z axis
O u tp u t
Shock
•
20 G 11 ms once each X, Y & Z axis
Output Power
•
500/1000 W for CPH500/1000
95-170 VAC
S a fe ty
Emissions
750/1500 W for CPH500/1000 with
input voltage 170-264 VAC
•
EN55022 Level B conducted
EN55022 Level B radiated
Output Voltage
Minimum Load
•
300-360 VDC (automatically changes
according to the input voltage)
External components required
Contact Sales for Application Note
•
•
No minimum load required
ESD Susceptibility
•
•
EN61000-4-2 Level 2
EN61000-4-2 Level 3
Overvoltage
Protection
390-440 VDC CPH500,
400-450 VDC CPH1000
Radiated
Susceptibility
Thermal Protection
Current Share
•
•
+100 °C ±15 °C (baseplate)
Standard
EFT/Burst
Surge
•
•
•
EN61000-4-4 Level 3
EN61000-4-5 Level 3, 4
EN60950, UL1950, CUL1950
Safety Approvals
G e n e ra l
Efficiency
Isolation
•
•
90/95% typical at 100/200 VAC
Input to Output not isolated,
3000 VAC Input to Ground
500 VDC Output to Ground
•
•
w w w .xp p lc .c o m
s a le s @xp p lc .c o m