3-line filters
B84143B/K*S080/S081
for converters and power electronics
Technical data and measuring conditions
Rated voltage VR
Type S080:
300/520 V AC (50/60 Hz)
Type S081:
440/760 V AC (50/60 Hz)
Rated voltage for IT mains supply
Type S080:
Type S081:
230/400 V AC (50/60 Hz)
320/560 V AC (50/60 Hz)
See also chapter "Technical information", section
8 "Energy supply networks".
Rated current IR
Referred to 40 °C rated temperature (250 A ... 1600 A)
Referred to 60 °C rated temperature (180 A)
Rated peak withstand current Ipk
Test voltage Vtest
According IEC 60439-1:2011, chapter 3.8.10.2;
limited by I2t characteristics of fuse
Type S080:
2240 V DC, 2 s (line/line)
2720 V DC, 2 s (lines/case)
Type S081:
3270 V DC, 2 s (line/line)
2890 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 ꢀ IR for 3 min per hour or
2.5 ꢀ IR for 30 s per hour
Leakage current lLK
Climatic category (IEC 60068-1)
Approvals
At VR and 50 Hz
25/100/21 (ꢁ25 °C/+100 °C/21 days damp heat test)
UL 1283; CSA C22.2 No.8
(Type *S080: 290/500 V; Type *S081: 350/600 V)