3-line filters for converters and power electronics

B84143D0090R127 技术参数

是否无铅: 不含铅是否Rohs认证: 符合
生命周期:ActiveReach Compliance Code:compliant
风险等级:5.84认证:UL; CSA; IEC
滤波器类型:THREE PHASE EMI FILTER高度:200 mm
高电位:2700 V最大漏电流:166 mA
长度:298 mm安装类型:PANEL MOUNT
工作频率:50/60Hz Hz物理尺寸:L298.0XB80.0XH200.0 (mm)/L11.732XB3.15XH7.874 (inch)
额定电流:90 A额定电压:530 V
宽度:80 mm

B84143D0090R127 数据手册

 浏览型号B84143D0090R127的Datasheet PDF文件第11页浏览型号B84143D0090R127的Datasheet PDF文件第12页浏览型号B84143D0090R127的Datasheet PDF文件第13页浏览型号B84143D0090R127的Datasheet PDF文件第14页浏览型号B84143D0090R127的Datasheet PDF文件第15页浏览型号B84143D0090R127的Datasheet PDF文件第17页 
3–line filters  
B84143D0xxxR127  
for converters and power electronics  
Caution and warnings  
S Please note the advices in our data book “EMC Filters” (latest edition); attention should  
be paid to the chapter “General safety notes”.  
S It shall be ensured that only qualified persons (electricity specialists) are engaged on work  
such as planning, assembly, installation, operation, repair and maintenance. They must  
be provided with the corresponding documentation.  
S Danger of electric shock. EMC filters contain components that store an electric charge.  
Dangerous voltages can continue to exist at the filter terminals for longer than five min-  
utes even after the power has been switched off.  
S The protective earth connections shall be the first to be made when the EMC filter is  
installed and the last to be disconnected. Depending on the magnitude of the leakage cur-  
rents, the particular specifications for making the protective–earth connection must be ob-  
served.  
S Impermissible overloading of the EMC filter, such as with circuits able to cause reso-  
nances, impermissible voltages at higher frequencies etc. can lead to bodily injury and  
death as well as cause substantial material damages (e.g. destruction of the filter hous-  
ing).  
S EMC filters must be protected in the application against impermissible exceeding of the  
rated currents by overcurrent protective.  
S In case of leakage currents > 3.5 mA you shall mount the PE conductor stationary with  
the required cross section before beginning of operation and save it against disconnect-  
ing. For leakage currents IL 4) < 10 mA the PE conductor must have a KU value 3) of 4.5;  
for leakage currents IL q 10 mA the PE conductor must have a KU value of 6.  
3) The KU value (symbol KU) is a classification parameter of safety–referred failure types designed to ensure protection against hazardous  
body currents and excessive heating.  
A value of KU = 4.5 with respect to interruptions is attained:  
2
– with a permanently connected protective earth circuit w 1.5 mm  
2
– with a protective earth circuit w 2.5 mm connected via shroud connectors (IEC 60309–2).  
2
KU = 6 with respect to interruptions is achieved for fixed–connection lines w 10 mm where the type of connection and line layout corre-  
spond to the requirements for PEN conductors as specified in relevant standards.  
4) I = leakage current let–go  
L
Please read Important notes and Cautions and  
warnings at the end of this document.  
Pa g e 1 6 o f 1 7  
B8 4 1 4 3D 0 xx xR 1 2 7-0 3 -7 6 5 9  

与B84143D0090R127相关器件

型号 品牌 描述 获取价格 数据表
B84143D0120R127 TDK Three Phase EMI Filter, 530V, 50/60HzHz, METAL PACKAGE

获取价格

B84143D0120R127 EPCOS 3-line filters for converters and power electronics

获取价格

B84143D0150R127 EPCOS 3-line filters for converters and power electronics

获取价格

B84143D0150R127 TDK 3-phase/3-Lines(520V), Rated Current:150A

获取价格

B84143D0200R127 EPCOS 3-line filters for converters and power electronics

获取价格

B84143D0200R127 TDK 3-phase/3-Lines(520V), Rated Current:200A

获取价格