2-line filters
B84142A/C/J*S081
for converters and power electronics
Technical data and measuring conditions
Rated voltage VR,L
Rated voltage VR,L
ꢀ
ꢀ
Type A*S081
Type C*S081
Type J*S081
1000 V DC
800 V DC
L
Gnd
1500 V DC
1500 V DC
1000 V DC
1000 V DC
Rated current IR
Referred to 40 °C rated temperature (250 A ... 1600 A)
Referred to 60 °C rated temperature (180 A)
Rated peak withstand current Ipk
Test voltage Vtest
According IEC 60439-1:2011, chapter 3.8.10.2;
limited by I2t characteristics of fuse
Type A*S081 and
Type J*S081
3270 V DC, 2 s (line/line)
2890 V DC, 2 s (lines/case)
Type C*S081
4200 V DC, 2 s (line/line)
4200 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 ꢁ IR for 3 min per hour or
2.5 ꢁ IR for 30 s per hour
Climatic category (IEC 60068-1)
Approvals
25/100/21 (ꢀ25 °C/+100 °C/21 days damp heat test)
UL 1283, CSA C22.2 No.8 (600 V AC)
Characteristics and ordering codes
IR
A
Ipk
kA
Terminal cross section Rtyp
Approx. weight
kg
Ordering code
Approvals
mm2
mΩ
VR = 1000 V DC
180
180
250
250
320
320
400
400
600
25
25
25
25
50
50
50
50
50
50
75
75
75
75
75
75
20 ×
20 ×
20 ×
20 ×
25 ×
25 ×
25 ×
25 ×
30 ×
30 ×
40 ×
40 ×
3
3
3
3
5
5
5
5
5
5
8
8
0.110 4.9
0.110 4.9
0.110 5.0
0.110 5.0
0.051 7.8
0.051 7.8
0.048 7.8
0.048 7.8
0.043 7.9
0.043 7.9
0.029 19.9
0.029 19.9
0.022 24.5
0.022 24.5
0.022 24.5
0.022 24.5
B84142A0180S081
B84142J0180S081
B84142A0250S081
B84142J0250S081
B84142A0320S081
B84142J0320S081
B84142A0400S081
B84142J0400S081
B84142A0600S081
B84142J0600S081
B84142A1000S081
B84142J1000S081
B84142A1250S081
B84142J1250S081
B84142A1600S081
B84142J1600S081
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
600
1000
1000
1250
1250
1600
1600
50 × 10
50 × 10
50 × 10
50 × 10
× = Approval granted for 600 V AC
Please read Cautions and warnings and
Important notes at the end of this document.
Page 4 of 17