MODEL: AS4T
R: 24 V DC
Plug-in Signal Conditioners M-UNIT
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
THERMOCOUPLE ALARM
(dual or quad alarm trip; field-configurable)
Functions & Features
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[3] OPTIONS (multiple selections)
Standards & Approvals
• Provides relay outputs at preset temperature levels
• Quad or dual trip
blank: CE marking
• Setting and display in engineering unit values
• Setpoint adjustments with the front keypad
• Software lock
/UL: UL approval, CE marking
Other Options
blank: none
• Adjustable hysteresis (deadband)
• On-delay timer
/Q: Option other than the above (specify the specification)
• Hi/Lo trip and energized/de-energized coil independently
selectable for each setpoint
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Enclosed relays
• Relays can be powered by 200 V AC and 100 V DC
• High-density mounting on DIN rail
/C02: Polyurethane coating
/C03: Rubber coating (UL not available)
TERMINAL SCREW MATERIAL
Typical Applications
• Annunciator
/S01: Stainless steel (UL not available)
EX-FACTORY SETTING
• Various alarm applications
50
(1.97)
/SET: Preset according to the Ordering Information Sheet
(No. ESU-1608)
80
(3.15)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
132
(5.20)
mm (inch)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Burnout: Upscale standard; downscale optional by
programming
MODEL: AS4T–[1]–[2][3]
Sampling cycle: 100 msec.
User-configurable items: Front key pad
• Alarm setpoint
ORDERING INFORMATION
• Code number: AS4T-[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. AS4T-2-R/UL/Q)
• Power ON-delay time
• Alarm ON-delay time
• Specify the specification for option code /Q
(e.g. /C01/SET)
• Moving average
• Hi/Lo trip operation
• Coil at alarm
[1] OUTPUT
• Hysteresis (deadband)
• Temperature range
2: 4 points; N.O. or make contact
3: 4 points; N.C. or break contact
5: 2 points; SPDT or transfer contact
• Temperature unit
• Thermocouple
• Others
(Refer to the instruction manual)
■ DISPLAY
[2] POWER INPUT
AC Power
LED: 8 mm (.31”) 7 segment, red
Number of display digits: 4 digits for DATA display;
2 digits for ITEM display
M2: 100 – 240 V AC, 50 – 60 Hz
(Operational voltage range 85 – 264 V, 47 – 66 Hz)
DC Power
AS4T SPECIFICATIONS
ES-1608 Rev.16 Page 1/4
https://www.m-system.co.jp/