Description (Continued)
Specifications (Continued)
PM-9 (Continued)
Output Current: 5 amperes max. continuous Standby
(when the PM-9 is used with any
AM-50 Series amplifier) (See Note 2)
Operating
Temperature:
Relative
32° to 120° F (0° to 49° C)
Humidity:
Supervised
0 to 93%, non-condensing at 90° F (32° C)
Non Power-Limited
Note 1: Continuous standby loads in excess of .560 Amps
up to 5 Amps may require a Generator Backup or load
shedding during an AC power failure.
Note 2: Continuous standby loads in excess of .560 Amps
up to 4 Amps may require a Generator Backup or load
shedding during an AC power failure.
Figure 4 PM-9G
PM-9G
The PM-9G is a switching power supply that provides 9
amps of filtered and regulated 24 VDC (nominal) to power
the INX transponder. It has an internal battery charging cir-
cuit capable of accommodating up to 55 A/H batteries as
well as an auxiliary continuous duty 24 VDC output @ 5
amps max.
Ordering Information
Part Number Description
Specifications
INX
Intelligent Network Transponder,
(Distributed Voice Network
Sub-Assembly Enclosure)
Transponder Voice Gateway
INX 9 ampere Power Supply
INX 9 ampere Power Supply
Description
PM-9G
INI-VGX
PM-9
PM-9G
Input Voltage: 240 VAC @ 50/60 Hz
Input Current: 2.4 amps max. @ 240 VAC, 50/60 Hz
Output Voltage: 24 VDC FWR
AM-50 Series:
AM-50-25
Output Current: 9 amperes Alarm max. continuous
Output Current: 5 amperes max. continuous Standby
(when the PM-9G is used with the ILI-E3
or the ILI95-E3 Series, see Note 1).
Output Current: 4 amperes max. continuous Standby
(when the PM-9G is used with any
AM-50 Series amplifier, see Note 2).
Operating
INX 50 watt 25 VRMS audio amplifier
INX 50 watt 70.7 VRMS audio amplifier
AM-50-70
Cabinets:
INX-CAB
Dimensions:
Backbox with Black Door
INX 19” W x 19” H x 4” D
(48 x 48 x 10 cm)
INX-CABR
Dimensions:
Backbox with Red Door
INX 19” W x 19” H x 4” D
(48 x 48 x 10 cm)
Temperature:
Relative
Humidity:
Supervised
32° to 120° F (0° to 49° C)
INX-CAB-B
Backbox with louvered door and
INX-CAB-B Mounting Plate
19 3/8” W x 19 3/8” H x 4.5” D
(49 x 49 x 11 cm)
0 to 93%, non-condensing at 90° F (32° C)
Dimensions:
Non Power-Limited:
Note 1: Continuous standby loads in excess of .560 Amps
up to 5 Amps may require a Generator Backup or load
shedding during an AC power failure.
Note 2: Continuous standby loads in excess of .560 Amps
up to 4 Amps may require a Generator Backup or load
shedding during an AC power failure.
Seismic Battery Bracket Kits
Part Number Description
90518
NetSOLO NS-INX 7 A/H Seismic Battery
Bracket Kit
90519
E3 CAB-C (INX only) 12 A/H Seismic
Battery Bracket Kit
PM-9
E3 CAB-D (INX only) 12 A/H Seismic
Battery Bracket Kit
Input Voltage: 120 VAC, 60 Hz
NetSOLO NS-INX 12 A/H Seismic
Battery Bracket Kit
Input Current: 4.6 amps max. @ 120 VAC 60 Hz
Output Voltage: 24 VDC FWR
For additional information on the Seismic Battery
Brackets, refer to the following documents:
Output Current: 9 amperes Alarm max. continuous
Output Current: 5 amperes max. continuous Standby
(when the PM-9 is used with the ILI-E3
•
•
Seismic Battery Bracket Installation Guide, P/N: 53839
E3 Series Cabinets Data Sheet, P/N: 9020-0649
or the ILI95-E3 Series, see Note 1).
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0541 Rev. M page 3 of 4