High Performance Thermal Circuit Breaker 4130-...
Description
Single pole high performance thermal circuit breaker, with push-to-reset
tease free, trip-free snap action mechanism (R-type TO CBE to EN
60934). Designed for threadneck panel mounting and for applications
with a high fault current switching requirement.
Approved to CBE standard EN 60934 (IEC 60934).
US patent number: US 6,040,747
Typical applications
Motors, transformers, solenoids, battery chargers, power supplies,
appliances, machinery, extra low voltage systems.
1
4130-...
Ordering information
Technical data
Type No.
4130 single pole thermal circuit breaker
Mounting
For further details please see chapter: Technical Information
Voltage rating
Current rating range
Typical life
AC 240 V; DC 50 V
20...80 A
G2 M12x1, knurled nut (bulk shipped with 5 pcs plus)
G4 M12x1, hex nut and knurled nut (bulk shipped with 5 pcs plus)
Number of poles
1
single pole, thermally protected
AC 240 V: 20...70 A 100 operations at 2 x IN, inductive
500 operations at 2 x IN, resistive
Actuator configuration
1
black push button
Terminal design
DC 50 V:
20...80 A 500 operations at 2 x IN, inductive
Ambient temperature
-30...+60 °C (-22...+140 °F)
K4 terminal M6x8
screw and washer bulk shipped
Characteristic curve
M1 medium delay
Current ratings
Insulation co-ordination
(IEC 60664)
rated impulse
withstand voltage
2.5 kV
pollution
degree
2
(reinforced insulation in the mounting area)
20... 80 A
Dielectric strength
operating area
test voltage
AC 3,000 V
4130 - G2
1
1 - K4 M1 - 20 A
ordering example
Insulation resistance
> 100 MΩ (DC 500 V)
800 A
Interrupting capacity Icn
Preferred types
Interrupting capacity
(UL 1077)
IN
UN
Preferred types
Standard current ratings (A)
20...80 A
20...60 A
80 A
20...50 A
60...80 A
AC 240 V
AC 120 V
AC 120 V
DC 50 V
DC 50 V
1,000 A
3,500 A
2,000 A
3,500 A
2,000 A
20 25 30 35 40 45 50 60 70 80
x
x
x
x
x
x
x
x
x
4130-G211-K4M1-
4130-G411-K4M1-
x
x
x
x
x
x
x
x
x
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
Standard current ratings and typical internal resistance values
Vibration
8 g (57-500 Hz) 0.61 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Current
rating (A)
Internal
Current
Internal
resistance (Ω)
Shock
25 g (11 ms)
to IEC 60068-27, test Ea
resistance (Ω) rating (A)
20
25
30
35
35
< 0.02
< 0.02
< 0.02
< 0.02
< 0,02
40
50
60
70
80
< 0.01
< 0.01
< 0.01
< 0.01
< 0,01
Corrosion
Humidity
Mass
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
approx. 55 g
Approvals
Authority
Standard
Rated voltage
Current ratings
VDE
IEC/EN 60934 AC 240 V
DC 50 V
20 A…70 A
20 A…80 A
UL
UL 1077
AC 240 V
DC 50 V
20 A…80 A
20 A…80 A
CSA
C22.2 No 235 AC 240 V
DC 50 V
20 A…80 A
20 A…80 A
1646
www.e-t-a.de
1