TMC 8...
Accessories1
Description
Type
Order No.
2908219
2908220
2908221
2908222
2908224
2908225
2908226
2908227
2908228
2907991
2907992
2907993
2907995
2907996
2907997
2907998
2907999
2908000
Pcs./Pkt.
Auxiliary contact, one NO and one NC switch
Alarm contact, one NO and one NC
TMC 7/8 AUX
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
TMC 7/8 ALARM
Shunt trip, 12 V DC, one NO and one NC
Shunt trip, 24 V DC, one NO and one NC
Shunt trip, 48 V DC, one NO and one NC
Shunt trip, 125 V DC, one NO and one NC
Shunt trip, 120 V AC, one NO and one NC
Shunt trip, 240 V AC, one NO and one NC
Shunt trip, 277 V AC, one NO and one NC
Busbar, cut to length, for 1-pole applications, up to 57 positions
Busbar, cut to length, for 1-pole plus auxiliary applications, up to 37 positions TMC 8 B1 80 37 CA
Busbar, cut to length, for 2-pole applications, up to 56 positions TMC 8 B2 80 56 C
Busbar, cut to length, for 2-pole plus auxiliary applications, up to 46 positions TMC 8 B2 80 46 CA
Busbar, cut to length, for 3-pole applications, up to 57 positions TMC 8 B3 80 57 C
Busbar, cut to length, for 3-pole plus auxiliary applications, up to 48 positions TMC 8 B3 80 48 CA
TMC 7/8 12VDC SHNT
TMC 7/8 24VDC SHNT
TMC 7/8 48VDC SHNT
TMC 7/8 125VDC SHNT
TMC 7/8 120VAC SHNT
TMC 7/8 240VAC SHNT
TMC 7/8 277VAC SHNT
TMC 8 B1 80 57 C
Busbar terminal, for incoming connections
Busbar, end cap, protects open busbar positions
Busbar, bus cap, protects three open busbar positions
TMC 8 B TERM PIN
TMC 8 B END CAP
TMC 8 B BUS CAP
1
For additional information on accessories, see “Accessories” on page 10.
3
Technical data
General data
Ambient temperature, operating
Permissible humidity
Degree of protection
Weight
-35°C … 70°C (-31°F … 158°F)
95%
IP20
134 g per pole (approximate)
NS35 rail (EN 60715)
1 ... 35 mm²/18 ... 2 AWG
Screw-clamp terminals
Installation
Conductor cross section
Connection type
Conductor tightening torque, maximum
2 Nm (17.7 lb -in.)
f
Electrical data
1
Nominal voltage, U
24 V DC ... 125 V DC
120 V AC ... 277 V AC
1 A ... 63 A
N
1
Nominal current
Service life
Mechanical
Electrical
20,000 cycles
6,000 cycles
Interrupt capacity I
UL 489 (SCCR)
IEC/EN 60947-2 (I
C
10 kA
10 kA
7.5 kA
)
)
CU
IEC/EN 60947-2 (I
1
CS
See order key for specifics for each model
3644_en_A
PHOENIX CONTACT
7/13