V-EA-Series - UL508 Manual Motor Controller - 1 pole D-Trip
V-EA-D Trip
0.3A Through 10A Rated Current
1.13-1.45xIN
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
Type/
Cat. No.
1DU03
1DU05
1DU075
NA
Approvals
U
UL508 Listed
60
40
L
E137938
U
L
10
U
L
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
U
L
U
L
1
1DU1
1DU1.6
1DU2
Standard Pack: 12
U
L
Weight:
10
4
U
L
0.3A - 32A
U
L
1DU2.5
1DU3
1.68kg (3.7 lb.)
40A - 63A
U
L
1
U
L
1DU3.5
1DU4
1DU5
0.4
1.92kg (4.23 lb.)
U
L
10-1
U
L
4x10-2
One Pole
U
L
1DU6
1DU8
10-2
U
L
4x10-3
U
L
1DU10
NA
NA
12A
10-3
1
2
3
4
5 6 8 10 1620
40
100
12.5A
13A
15A
Multiple of Rated Current
U
L
1DU13
1DU15
1DU16
1DU20
1DU25
1DU30
1DU32
1DU40
1DU50
1DU60
1DU63
U
L
91.5 mm
(3.60 in.)
35 mm
U
L
(1.38 in.)
16A
20A
V-EA-D Trip
13A Through 63A Rated Current
1.13-1.45xIN
U
L
U
L
25A
30A
60
40
U
L
U
L
32A
40A
10
70 mm
Thermal Overload
“Must Trip” < 1 hr = 145% RC
U
L
17.5 mm
(0.69 in.)
4
(2.76 in.)
“Must Not Trip” > 1 hr = 113% RC
1
U
L
50A
60A
U
L
63A
10
4
For ring tongue terminal version, replace “U”
with “R” in part number. For example 1BR20
instead of 1BU20.
1
0.4
Voltage Rating
277VAC
0.3-25A: 1 pole - 42VDC
30-60A: 1 pole - 24VDC
10-1
4x10-2
10-2
4x10-3
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
Short Circuit Withstand Rating
(UL/CSA - Ratings)
10-3
1
2
3
4
5 6 8 10 1620
40
100
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Multiple of Rated Current
0.3-63A (RC): 10kA
Interrupting Capacity (VDE - Ratings)
40°C (104°F)
Calibration Temperature
Terminal Size Acceptability
Terminal Torque
Top: 18-3 AWG; Bottom: 18-2 AWG
20 lb.in.
IP20
Terminal Protection Degree
short circuit Withstand ratings for v-ea manual motor controller
Backup
Protection
UL-Listed
RK5-Fuse
up to 10kA
UL-Listed
MCCB
up to 10kA
No BCP
Required
up to:
Trip
Curve
Amp Range
0.3 - 10A
all
all
all
all
4xRC*
min 15A, max 70A
4xRC*
min 15A, max 70A
10kA
5kA
5kA
5kA
12 - 30/32A
40 - 50A
4xRC*
max 125A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 200A
60 / 63A
4xRC*
max 250A
4xRC*
max 250A
*up to nearest rated current