100ACMEB Series
100W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated
AC-DC Converter
100 Watt
Universal input: 90~264VAC
Regulated output, low ripple
and noise
Over voltage protection (OVP)
Meets EN60950, UL60950
UL / IEC / EN 60601 3.1
Edition & UL / IEC / EN 60950
AM2 Safety Approvals
Meets EN60601-1, ANSI/
AAMI ES60601-1 standards
(2 x MOOP)
The 100ACMEB series is a compact size power converter offered by
GAPTEC. It features universal input voltage, taking both DC and AC
input voltage, low power consumption, high efficiency, high reliability,
safer isolation. It offers good EMC performance, meets IEC/EN61000-4,
CISPR22/EN55022, UL60950 and EN60950 standards, and is widely used
in medical instrumentation and critical applications in commercial and
industrial electronic equipment.
High efficiency up to 90%
Short circuit protection (SCP)
Output power protection (OPP)
With PFC Function >0.9
<0.3W No Load Input Power
(pending)
Approval
Model
Power
[W]
Output voltage
[V]
Output current
[mA, max]
Capacitive Load
[µF, max]
Efficiency
[@230VAC, %, typ]
UL/CE
UL/CE
UL/CE
100ACMEB_12S4
100ACMEB_24S4
100ACMEB_48S4
100
100
100
12
24
48
6666
4167
2083
3000
1500
500
90
90
90
Input specifications
Output specifications
Input voltage range
90-264 VAC
Item
Test conditions
Min Typ
2
Max
160
Units
%
“ N ” to DC “ + “ ; “L ” to DC “ - “
Output voltage
accuracy
Full load
Input frequency
Input current
47~63Hz
115VAC
• 2A (max)
230VAC
• 1A (max)
Line regulation
Load regulation
Ripple & noise*
1
1
%
10% to 100% load
%
Inrush current
(<2ms)
115VAC
• 45A (typ)
230VAC
• 90A (typ)
• 100ACMEB_12S4
• Others
mV
1% of Vout
Leakage current
< 0.1mA/264VAC (touch current)
>0.97 (115 VAC) / PF>0.9 (230 VAC)
Hold-up time
@90% Vout/115VAC
10
ms
Power factor
(at full load)
* Measured at 20MHz of bandwidth with 0.1uF & 47uF parallel capacitor.
Protection specifications
Example:
100ACMEB_05S4
Short circuit
protection
Protection type:
Auto recovery, hiccup mode
100 = 100Watt; AC = AC-DC; MEB = series; 5Vout; S = Single Output;
4 = 4kVAC
Over-voltage
protection
Protection type:
Auto recovery, hiccup mode
Over-power
protection
Protection type:
Note:
Auto recovery, hiccup mode
1. This product is not designed for use in critical life support systems, equipment
used in hazardous environment, nuclear control systems or other such
applications which necessitate specific safety and regulatory standards other
the ones listed in this datasheet.
Over-temperature
protection
Protection type:
Latch off
2. All specifications valid at 230VAC input voltage, full load and +25°C after
warm-up time unless otherwise stated.
Page 1 of 3
100ACMEB – Rev. 2017-1.0
Specifications subject to change without notice.
GAPTEC-Electronic GmbH & Co. KG
sales@gaptec-electronic.com – www.gaptec-electronic.com