UT 6-TMC M...
Thermomagnetic circuit breakers
CLIPLINE
Data sheet
103943_en_04
© PHOENIX CONTACT 2010-08-18
1
Description
The UT 6-TMC M circuit breaker is a single-position
overload circuit breaker with thermomagnetic tripping. It is a
space-saving circuit breaker with trip-free mechanism in the
event of overload and short circuits within the maximum
interrupting rating. The UT 6-TMC M is mounted on an
NS 35 DIN rail.
UT 6-TMC M thermomagnetic circuit breakers feature a
compact design, large labeling areas, and a double plug-in
bridge shaft.
The circuit breakers provide a high level of system
availability thanks to their reclosure function and clear status
display.
Eleven nominal current versions can be selected from 0.5 A
to 16 A. The large center labeling area enables clear
assignment of the relevant circuit breaker.
NOTE: The magnetic tripping ranges differ for alternating currents (AC) and direct currents (DC) (see page 3). The
magnetic operating currents for direct currents (DC) are approximately 1.6 times higher.
NOTE: When mounted in rows with simultaneous load, a mutual thermal effect occurs (see page 4).
Calibration is required for an ambient temperature of +23°C. A correction factor must be used to determine the
nominal current for a lower or higher ambient temperature (see page 5).
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for all products listed on the following page: