Voltage Sensitive Relays
WILMAR™ Protective Relays – WOUVT Series, Over/Undervoltage
27/59
Function:
• ANSI/IEEE C37.90-1978
Voltage sensitive relays are available for both AC
and DC applications for overvoltage and undervoltage
protection. Combination over/undervoltage relays
provide band-pass capabilities. AC relays are either
single or three-phase type. Three phase relays are
designed to sense the average of the three phases.
Voltage trip points are screwdriver adjustable, and
operation is time-delayed so that momentary volt-
age transients will not cause nuisance tripping.
TERMINAL STRIP
#6 - 32 SCREWS
3.0
Operation:
The relay will energize at normal voltage condition.
The normally closed contact (Form B) will open and
the normally open (Form A) will close. The relay will
de-energize after time delay when over or undervoltage
condition is reached.
11
/
64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PART NUMBER SELECTION
Sample Part No.
Type:
WOUVT -1-120AC
WOUVT - Over/Undervoltage
No. Phases
1 = Single
3 = Three (line to line)
Line Voltage VAC
PRODUCT SPECIFICATIONS
400
416
440
460
480
525
575
115
120
Part Number
WOUVT
200
Nominal Voltage ...............................
Phase ................................................
Line Frequency .................................
Type of Sensing ...............................
Undervoltage Trip ............................
Overvoltage Trip ...............................
Drop-out Time Delay........................
Pick-up to Drop-out Differential ......
Output Contacts ...............................
Contact Ratings ................................
Operating Temperature Range ........
Power Consumption ........................
120 VAC to 575 VAC
208
Single or Three
220
230
50-400 Hz
240
Average of all three phases
70-100% of nominal voltage, screwdriver adjustable
100-125% of nominal voltage, screwdriver adjustable
0.5 to 20 seconds, screwdriver adjustable
2% maximum
380
Options:
Blank - Standard
A = 2 Form A Contacts
B = 2 Form B Contacts
H = 125 VDC Contacts
P = Transient Protection
One set N.O., One set N.C.
5 amp resistive at 120 VAC or 28 VDC
-40°C to +70°C
Option "H" provides for contacts rating of 3 amps @
125VDC.
Option "P" provides additional transient protection which
complies with the requirements of ANSI/IEEE C37.90-
1978
4 VA maximum
Notes:
1. Remove black screw for access to the voltage trip and time delay adjustment potentiometer.
2. Clockwise rotation of the voltage adjustment potentiometer will raise the voltage trip point.
3. Clockwise rotation of the time adjustment potentiometer will increase the drop-out time delay.
Consult factory for additional models.