UHP-12/21-D48
IsNolateOd, 2T1 AmRpEHalCf BrOick,M48VIMN/12EVONUT DDC/DEC CDonverter
ORDERING GUIDE SUMMARY
Model
VOUT Range
IOUT Range
VIN Range
Ripple/Noise
Efficiency
FOR NEW DESIGNS
UHP-12/21-D48
12V
0-21A
36-75V
125mVp-p
91%
INPUT CHARACTERISTICS
Parameter
Typ. @ 25°C, full load
36-75 Volts
5.77 Amps
33 Volts
Notes
Voltage Range
48V nominal
VIN = 48V
Current, full power
Undervoltage Shutdown
Short Circuit Current
Remote On/Off Control
20mA
VIN = 48V
0 to +VIN
Positive or negative logic
OUTPUT CHARACTERISTICS
Parameter
FEATURES
Typ. @ 25°C, full load
12 Volts 10%
0 to 21 Amps
255 Watts max.
1.25%
Notes
Voltage
Trim range shown
No minimum load
■
Wide 36-75V input range
Current
■
12V output @ 21 Amps. max.
Power Output
Maximum baseplate = +110°C @ 255W
■
Very high efficiency of 91%
Accuracy
■
Operates to +110°C baseplate w/derating
Ripple & Noise
125mVp-p
0.05%/ 0.25%
30 Amps
20MHz bandwidth
Line and Load Regulation
Overcurrent Protection
Overtemperature Protection
Efficiency (minimum)
Efficiency (typical)
■
Conduction-cooled baseplate, no fans
With hiccup auto-restart
■
Industry-standard mounting and pinout
+125°C
■
Remote sense, trim and On/Off control
90%
■
Isolated to 2250Vdc (Basic insulation)
91%
■
Multiple I/O protection features
GENERAL SPECIFICATIONS
Parameter
■
UL/EN60950 safety approvals, CE mark
Typ. @ 25°C, full load
150μsec
Notes
■
Start up into pre-biased load
Dynamic Load Response
Operating Temperature Range
Operating Temperature Range
Safety
50-75-50% step to 1.5% of final value
With baseplate, see derating curve
Without baseplate
–40 to +110°C
–40 to +32°C
DESCRIPTION
For “distributed architecture” power applications,
DATEL’s UHP-12/21-D48 DC/DC converter offers
a wide input range of 36-75 Volts DC, delivering
up to 21 Amps with 12 Volts DC output. This DC/
DC converter is an ideal precision intermediate
bus power unit with tight regulation and 2250
Volt isolation. It is manufactured on a 2.3" x 2.4"
open-frame package with industry-standard “half
brick” pinout and mounting.
UL/IEC/EN 60950
And CSA C22.2-No.60950
MECHANICAL CHARACTERISTICS
With baseplate
2.30 x 2.40 x 0.502 inches (58.42 x 60.96 x 12.75 mm)
2.30 x 2.40 x 0.452 inches (58.42 x 60.96 x 11.48 mm)
Without baseplate
plate temperature. Multiple protection features
avoid damage to outside equipment and to the
converter itself. The converter will shut down on
sustained input undervoltage, output overcurrent,
output short circuit and overvoltage and thermal
shutdown. Overload currents less than a short
circuit limit the output current so that operation
is not interrupted. Upon short circuit shutdown,
the converter will automatically attempt to restart
(“hiccup” mode) when the overload is removed.
The overall unit is designed to be as “lead-free”
as practical in construction and attachment
method (no lead added in assembly). Standard
features also include Sense and Trim pins and
On/Off Control.
UHP converters use a interleaved forward, fixed-
frequency topology with synchronous output recti-
fication to achieve high efficiency. UHP-12/21-D48
can be operated using conduction cooling
attached to a housing wall or system heat sink.
No forced air-flow is needed to +110°C base-
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000
UHP-12/21-D48.B02 Page 1 of 12