MODEL: R3S-RR8
/C03: Rubber coating
Remote I/O R3 Series
RELATED PRODUCTS
• Interface Module (model: R3-NC1, NC3, NE1, NM1, NDx,
REMOTE CONTROL RELAY CONTROL MODULE
(Do 8 points, tension clamp terminal block)
Functions & Features
NF2, NFL1)
Firmware version V2.00 or higher.
• Controls remote control relays for lighting control with
Fieldbus
R3-NF2 is available with firmware version V0.04 or higher.
• Applicable to the remote control relays already installed
• Monitors status of remote control relays with feedback
inputs from signal lines
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Output: Separable tension clamp terminal (applicable wire
Typical Applications
• Monitors and controls of lighting in buildings
size: 0.2 to 1.5 mm , stripped length 10 mm)
2
Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Output to internal bus or internal power
Input Data Length: 8 bit, 16 bit selectable with DIP switch
Output data length: 8 bit, 16 bit selectable with DIP switch
RUN indicator: Bi-color (red/green) LED;
27.5 (1.08)
130 (5.12)
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED;
120 (4.72)
mm (inch)
OFF in abnormality; ON in normal operating conditions.
Input output status indicator: Red LED;
1 to 8: Output bit status, turns on with bit set ON.
9 to 16: Feedback input status, turns on with the input ON.
MODEL: R3S-RR8[1][2]
OUTPUT SPECIFICATIONS
Number of output: 8 points
ORDERING INFORMATION
• Code number: R3S-RR8[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3S-RR8W/Q)
Common: All 8 points (12 terminal)
Rated load voltage: 24 V AC ±10 % (supplied by the remote
control transformer)
• Specify the specification for option code /Q
(e.g. /C01)
Load voltage frequency: 50 / 60 Hz
Maximum outputs provided at once: No limit
Output ON duration: 100 msec.
NO. OF CHANNELS
8: 8
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
[1] COMMUNICATION MODE
S: Single
W: Dual
[2] OPTIONS
blank: none
PERFORMANCE
Data allocation: 1
/Q: Options other than the above (specify the specification)
Current consumption: 40 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
R3S-RR8 SPECIFICATIONS
ES-8934 Rev.3 Page 1/5
http://www.m-system.co.jp/