G7SA
Options (order separately)
Sockets
Push-In Plus terminals
4 poles 6 poles
Models P7SA-10F-ND-PU P7SA-14F-ND-PU
• With operation indicator LED/built-in diode
Screw terminals
PCB terminals
4 poles 6 poles
P7SA-14P
4 poles
P7SA-10F(-ND)
6 poles
Items
P7SA-14F(-ND)
P7SA-10P
P7SA-@F-ND(-PU): −20 to +70°C
−40 to +85°C
(with no icing or condensation)
Ambient operating temperature
• Without operation indicator LED/built-in diode
P7SA-@F:
−40 to +85°C
(with no icing or condensation)
Ambient operating humidity
Continuous carry current
25% to 85%
5% to 85%
6 A *1
Between coil and
contact terminals
Between contact
4,000 VAC for 1 min.
2,500 VAC for 1 min.
2,500 VAC for 1 min.
Dielectric terminals of different
strength
polarity
Between contact
terminals of same
polarity
1,500 VAC for 1 min.
Insulation resistance
Weight
1,000 MΩ min. *2
Approx. 58 g
Approx. 70 g
Approx. 44 g
Approx. 59 g
Approx. 9 g
Approx. 10 g
*1. When operating the P7SA-@F-ND-PU at a temperature between 50 and 70°C, reduce the continuous current (6 A at 50°C or less) by 0.25 A
for each degree above 50°C.
When operating the P7SA-@F-ND at a temperature between 50 and 70°C, reduce the continuous current (6 A at 50°C or less) by 0.3 A for
each degree above 50°C.
When operating the P7SA-@F at a temperature between 50 and 85°C, reduce the continuous current (6 A at 50°C or less) by 0.1 A for each
degree above 50°C.
*2. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
Short Bars (for P7SA-@F-ND-PU)
Ambient operating
temperature
Ambient operating
humidity
Application
Applicable sockets
Models
Maximum carry current
XW5S-P2.5-2@
XW5S-P2.5-3@
XW5S-P2.5-4@
XW5S-P2.5-5@
Crossover wiring of
contact terminals
(bottom)
P7SA-@F-ND-PU
24 A
−40 to 55°C
5% to 95%
Certified Standards
Safety Relay Unit
EN Standards, VDE Certified
Ratings
Standard number
Certification No.
Operating coil
Contact ratings
Models
G7SA-2A2B
EN/IEC 61810-1
Electromagnetic relay
EN/IEC 61810-3
Relays with forcibly guided
contacts
G7SA-3A1B
G7SA-3A3B
G7SA-4A2B
G7SA-5A1B
12, 18, 21, 24, 48,
110 VDC
12, 18, 21, 24, 48,
110 VDC
6 A, 240 VAC (Resistive)
6 A, 30 VDC (Resistive)
125547
UL Standards Certification (File No. E41515) Industrial Control Devices
Standard number
Category
Listed/Recognized
Contact ratings
Operating Coil ratings
Models
G7SA-2A2B
G7SA-3A1B
G7SA-3A3B
G7SA-4A2B
G7SA-5A1B
6 A, 250 VAC (Resistive)
6 A, 30 VDC (Resistive)
12, 18, 21, 24, 48,
110 VDC
UL508
E41515
Recognized
CSA standard CSA C22.2 No.14 Industrial Control Devices
Class number
File No.
Contact ratings
Operating Coil ratings
Models
G7SA-2A2B
G7SA-3A1B
G7SA-4A2B
G7SA-5A1B
6 A, 250 VAC (Resistive)
6 A, 30 VDC (Resistive)
12, 18, 21, 24, 48,
110 VDC
3211-07
LR35535