G7SA
Specifications
Ratings
Safety Relay Unit
Coil (4 poles)
Contacts
Item
Rated
Coil
Max.
Power
Item
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Contact materials
Load
Resistive load
6 A at 210 VAC, 6 A at 30 VDC
6 A
current resistance voltage consumption
(mA)
30
20
±7.±
±1
Rated voltage
12 VDC
(Ω)
400
(V)
(mW)
210 VAC, ±21 VDC
6 A
Au plating + Ag alloy
18 VDC
21 VDC
24 VDC
48 VDC
900
±,221
±,600
6,400
28,8±0
Approx. 360
Approx. 420
Power
±±05
7.1
3.8
110 VDC
Coil (6 poles)
Item
Rated
Coil
Max.
current resistance voltage consumption
Rated voltage
12 VDC
(mA)
4±.7
27.8
23.8
20.8
±0.4
1.3
(Ω)
288
648
882
±,±12
4,606
20,862
(V)
(mW)
18 VDC
21 VDC
24 VDC
48 VDC
Approx. 100
±±05
110 VDC
Approx. 180
Note: 1. The rated current and coil resistance are measured at a coil
temperature of 23°C with tolerances of ±±15.
2. The maximum voltage is based on an ambient operating
temperature of 23°C maximum.
Characteristics
Safety Relay Unit
Contact resistance *1
Operating time *2
Response time *3
Release time *2
±00 mΩ max.
20 ms max.
±0 ms max.
20 ms max.
Must operate voltage
715 max.
Must release voltage
±05 min.
Mechanical
Rated load
Insulation resistance *4
Betweencoiland
36,000 operations/h
±,800 operations/h
±,000 MΩ min.
Maximum operating
frequency
4,000 VAC, 10/60 Hz for ± min.
contacts
Between
contacts of
4,000 VAC, 10/60 Hz for ± min. (except for followings)
4 poles (for poles 3-4 in 4-pole Relays),
Dielectric Strength
*5 *6
different polarity 6 poles (for poles 3-1, 4-6, and 1-6 in 6-pole Relays): 2,100 VAC, 10/60 Hz for ± min.
Between contacts
±,100 VAC, 10/60 Hz for ± min.
of the same polarity
Vibration resistance
Shock resistance
±0 to 11 to ±0 Hz, 0.71-mm single amplitude (±.1-mm double amplitude)
Destruction
Malfunction
Mechanical
Electrical
±,000 m/s2
±00 m/s2
±0,000,000 operations min. (at approx. 36,000 operations/h)
±00,000 operations min. (at the rated load and approx. ±,800 operations/h)
Durability *7
Inductive load switching capability *8
(IEC60947-5-1)
AC±1 240 VAC, 2 A
DC±3 24 VDC, ± A/48 VDC, 0.1 A/±±0 VDC, 0.2 A
Failure rate (P level)
(reference value *9)
1 VDC, ± mA
±2 to 48 VDC: -40 to 81°C (with no icing or condensation)
Ambient operating temperature *10
Ambient operating humidity
Weight
±±0 VDC:
-40 to 60°C (with no icing or condensation)
15 to 815
4 poles: Approx. 22 g
6 poles: Approx. 21 g
Note: 1. The above values are initial values.
2. Performance characteristics are based on coil temperature of 23°C.
*1. The contact resistance was measured with ± A at 1 VDC using the voltage-drop method.
*2. These times were measured at the rated voltage and an ambient temperature of 23°C. Contact bounce time is not included.
*3. The response time is the time it takes for the normally open contacts to open after the coil voltage is turned OFF. Contact bounce time is
included. Measurement conditions: Rated voltage operation, Ambient temperature: 23°C
*4. The insulation resistance was measured with a 100-VDC megohmmeter at the same locations as the dielectric strength was measured.
*5. Pole 3 refers to terminals 3±-32 or 33-34, pole 4 refers to terminals 43-44, pole 1 refers to terminals 13-14, and pole 6 refers to terminals 63-64.
*6. When using a P7SA Socket, the dielectric strength between coil contacts/different poles is 2,100 VAC, 10/60 Hz for ± min. When using Push-In Plus
terminal sockets (P7SA-@F-ND-PU), the dielectric strength between coil contacts as well as between different poles is 4,000 VAC, 10/60 Hz for ± min.
*7. The durability is for an ambient temperature of ±1 to 31°C and an ambient humidity of 215 to 715. For the durability performance to the load,
refer to the Durability Curve.
*8. AC±1: cosφ = 0.3, DC±3: L/R = 48-ms.
*9. The failure rate is based on an operating frequency of 300 operations/min.
*10. ±2 to 48 VDC: When operating between 70 and 81°C, reduce the rated carry current of 6 A by 0.± A for each degree above 70°C.
±±0 VDC: When operating between 40 and 60°C, reduce the rated carry current of 6 A by 0.27 A for each degree above 40°C.
4