■ Characteristics
Contact resistance
100 mΩ max.
20 ms max.
Operate time
Release time
20 ms max.
Max. operating frequency
Mechanical 18,000 operations/hr
Electrical
1,800 operations/hr (under rated load)
Insulation resistance
Dielectric withstand voltage
Vibration resistance
1,000 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1.0 min (1,000 VAC between contacts of same polarity)
Destruction:10 to 55 Hz, 1.0 mm double amplitude
Malfunction:10 to 55 Hz, 1.0 mm double amplitude
Destruction:1,000 m/s2 (approx. 100G)
Shock resistance
Malfunction:200 m/s2 (approx. 20G)
Life expectancy
Ambient temperature
Ambient humidity
Weight
See the following table.
Operating
Operating
-55°C to 70°C (-67°F to 158°F) with no icing (see note)
5% to 85% RH
Approx. 35 g
Note: The values given above are initial values.
■ Life Expectancy Characteristics
Pole
Mechanical life
(at 18,000 operations/hr)
Electrical life
(at 1,800 operations/hr under rated load)
2-pole
AC:50,000,000 operations min.
DC:100,000,000 operations min.
500,000 operations min.
200,000 operations min.
100,000 operations min.
4-pole
4-pole (bifurcated)
20,000,000 operations min.
■ Approved Standards
VDE, UL, CSA, CE
(CE marking is provided only on non-PCB terminal versions)
■ Precautions
Connections
Do not reverse polarity when connecting DC-operated Relays with
built-in diodes or indicators or high-sensitivity DC-operated Relays.
Mounting
Whenever possible, mount Relays so that it is not subject to vibration
or shock in the same direction as that of contact movement.
General-purpose Relay MY