Current Transducer LA 205-S
IPN = 200 A
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
IPN
IP
Primary nominal r.m.s. current
200
0 .. ± 300
600
A
A
A
Features
Primary current, measuring range
1)
ÎP max Measuring overload
RM
· Closed loop (compensated) current
transducer using the Hall effect
· Insulated plastic case recognized
according to UL 94-V0
Measuring resistance @
TA = 70°C
RM minRM max RM minRM max
TA = 85°C
with ± 12 V
with ± 15 V
@ ± 200 A max
@ ± 300 A max
@ ± 200 A max
@ ± 300 A max
0
0
5
5
68
33
95
50
0
0
5
5
66
30
93
49
W
W
W
W
· Patent pending.
Advantages
ISN
KN
VC
IC
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
R.m.s rated voltage 2), safe separation
basic isolation
100
1 : 2000
± 12 .. 15
20 (@ ±15 V) + IS mA
1625
3250
mA
· Excellent accuracy
· Very good linearity
V
· Low temperature drift
· Optimized response time
· Wide frequency bandwidth
· No insertion losses
· High immunity to external
interference
Vb
V
V
Accuracy - Dynamic performance data
· Current overload capability.
X
Overall accuracy @ IPN , TA = 25°C
Linearity
± 0.8
< 0.1
%
%
eG
L
Applications
Typ Max
IO
IOM
IOT
Offset current @ IP = 0, TA = 25°C
± 0.15 mA
± 0.50 mA
± 0.15 ± 0.30 mA
· AC variable speed drives and servo
motor drives
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies
(UPS)
Residual current 3) @ IP = 0, after an overload of 3 x IPN
Thermal drift of IO
- 10°C .. + 85°C
tra
tr
Reaction time @ 10 % of IPN
Response time 4) @ 90 % of IPN
< 500
< 1
ns
µs
di/dt di/dt accurately followed
f
> 100
DC .. 100
A/µs
kHz
Frequency bandwidth (- 3 dB)
· Switched Mode Power Supplies
(SMPS)
General data
· Power supplies for welding
applications.
TA
TS
RS
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance @
- 10 .. + 85
- 40 .. + 90
35
37
110
°C
°C
W
W
g
TA = 70°C
TA = 85°C
m
Mass
Standards 5)
EN 50178
1)
Notes : 3 mn/hour @ VC = ± 15 V, R M = 5 W
2)
Pollution class nr 2. With a non insulated primary bar which fills the
through-hole
The result of the coercive field of the magnetic circuit
With a di/dt of 100 A/µs
3)
4)
5)
020711/6
A list of corresponding tests is available
LEM Components