描述
2U Rack Mount, Output: 15kW, 0 to 1000V

GSPL1000-15-3P480 数据手册

 浏览型号GSPL1000-15-3P480的Datasheet PDF文件第1页浏览型号GSPL1000-15-3P480的Datasheet PDF文件第3页浏览型号GSPL1000-15-3P480的Datasheet PDF文件第4页浏览型号GSPL1000-15-3P480的Datasheet PDF文件第5页浏览型号GSPL1000-15-3P480的Datasheet PDF文件第6页浏览型号GSPL1000-15-3P480的Datasheet PDF文件第7页 
The  
family of programmable power supplies sets a new standard for flexible, reliable,  
AC/DC power systems in OEM, Industrial and Laboratory applications.  
Features include:  
Leading DC Programmable power density (15kW/22.5kW in 2U/3U height) in 19” rack-mount  
Light-weight GSPL 15kW<18 kg, 22kW<25 kg  
Wide Range of popular worldwide AC inputs:  
GSPL10kW / GSPL15kW: 3ø (208VAC, 480VAC), Wide-range 3ø 208VAC (170VAC ~ 265VAC  
)
Wide-range 3ø 480VAC (342VAC ~ 528VAC  
Active PFC (0.94 typical)  
Output Voltage up to 1500V, Current up to 1125A  
Built-in LAN ( 1.5), USB, RS-232/RS-485 Interface  
Multi-Drop capability (RS-485)  
Multi-functional front panel display  
Last-Setting Memory  
Auto-Start / Safe-Start: user selectable  
High Resolution 16 bit ADCs & DACs  
Arbitrary Waveform Generator with Auto-Trigger Capability  
Store up to 100 steps into four internal memory cells  
High-speed Programming  
Constant Voltage/Constant Current operation modes  
Constant Power (CP) Limit  
)
Slew-Rate Control (V/I)  
Internal Resistance Programming Simulation  
Local / Remote Sensing - software controlled  
Built-In Remote Isolated Analog Program/Monitor and Control Interface  
Protection functions (OVP, UVP, UVL, FOLD (CV/CC), OCL, OTP, AC FAIL)  
Fan speed controlled by ambient temperature and load  
Certified LabWindows™/CVI, LabVIEW™, and IVI Drivers  
Optional EtherCAT, Modbus-TCP, IEEE (488.2) Interfaces  
19" Rack Mount capability for ATE and OEM application  
Scalable Power Systems of 15kW and 22.5kW  
Parallel Systems (up to 90kW) with Auto-Configure  
Worldwide Safety Agency approvals  
CE Mark for Low Voltage, EMC and RoHS3 Directives  
Five year warranty  
Applications  
power supplies have been designed to meet the demands of a wide variety of applications.  
Test & Measurement systems, Component Device Testing, Manufacturing and process control.  
Semiconductor Processing & Burn-In, Aerospace & Satellite Testing, Medical Imaging, Green Technology.  
Higher power systems can be configured with up to four (4) GSPL 22.5kW units. Each unit is 3U with zero  
space between them (zero stack).  
OEM Designers have a wide variety of Inputs and Outputs from which to select depending on application  
and location.  
3
GSPL15kW Front Panel Description  
3
4
3
2
1
5
6
1. Input Power ON/OFF Switch  
2. Air Intake allows zero stacking for maximum system flexibility and power density.  
3. Reliable Detent Encoders for settings and Menu navigation.  
4. High Contrast/Brightness display with wide viewing angle, 16 segment LCD  
5. Function/Status LEDs: Active modes and function indicators  
6. Pushbuttons allow flexible user configuration  
GSPL15kW Rear Panel Description  
9
11  
10  
12  
4
5
6
7
8
1
2
3
1. Isolated Analog Programming, Monitoring and other control connector (DB26 Female)  
2. USB Interface connector (Type B).  
3. RS-232/RS-485 IN/OUT Remote Digital Interface (RJ-45 type) for Multi-Drop connection  
4. LAN (  
1.5) Interface connector (RJ-45 type with LAN status indicators).  
5. Auto paralleling Bus connectors (mini I/O type) for connecting Master unit-to-Slave and Slave unit-to-Slave unit.  
6. Remote/Local Output Voltage Sense Connections (PHOENIX CONTACT GIC 2,5 HCV/3-ST-7,62 ).  
7. Output Connections: Rugged busbars (shown) for models up to and including 1500V Output;  
8. Input Connector: 208VAC, 480VAC Three Phase, 50/60 Hz.  
AC Input Plug Connector: PHOENIX CONTACT DFK-IPC 16/4-STF-10.16 with strain relief.  
9. Optional Interface Position for IEEE 488.2 SCPI or AnyBus Interface.  
10. Exhaust air assures reliable operation when zero stacked.  
11. Functional Ground connection (M4x8mm stud).  
12. Reset button. Set default Power Supply settings.  
4
GSPL22.5kW Front Panel Description  
4
3
3
2
1
5
6
1. Input Power ON/OFF Switch  
2. Air Intake allows zero stacking for maximum system flexibility and power density.  
3. Reliable Detent Encoders for settings and Menu navigation.  
4. High Contrast/Brightness display with wide viewing angle, 16 segment LCD  
5. Function/Status LEDs: Active modes and function indicators  
6. Pushbuttons allow flexible user configuration  
GSPL22.5kW Rear Panel Description  
9
11  
10  
12  
4
5
6
1
2
3
7
8
1. Isolated Analog Programming, Monitoring and other control connector (DB26 Female)  
2. USB Interface connector (Type B).  
3. RS-232/RS-485 IN/OUT Remote Digital Interface (RJ-45 type) for Multi-Drop connection  
4. LAN (  
1.5) Interface connector (RJ-45 type with LAN status indicators).  
5. Auto paralleling Bus connectors (mini I/O type) for connecting Master unit-to-Slave and Slave unit-to-Slave unit.  
6. Remote/Local Output Voltage Sense Connections (PHOENIX CONTACT GIC 2,5 HCV/3-ST-7,62).  
7. Output Connections: Rugged busbars for models up to and including 1500V Output;  
8. Input: 208VAC, 480VAC Three Phase, 50/60 Hz.  
AC Input Plug Connector: 3-Phase 208: PC 35 HC/ 4-GF-15,00 Phoenix Contact.  
3-Phase 480: DFK-PC 16/ 4-STF-10, 16 PHOENIX CONTACT.  
9. Optional Interface Position for IEEE 488.2 SCPI or AnyBus Interface.  
10. Exhaust air assures reliable operation when zero stacked.  
11. Functional Ground connection (M4x8mm stud).  
12. Reset button. Set default Power Supply settings.  
5
Front Panel Display MENU/CONTROL buttons:  
Voltage  
Encoder  
(Clickable)  
Current  
Encoder  
(Clickable)  
MENU buttons and  
Output Control buttons  
and Status LEDs  
Active menu LEDs  
Output ON/OFF  
Status LED  
Back  
Alarm LED  
Program  
Menu  
System  
Menu  
Voltage/Current  
Preview mode  
FINE  
Output setting  
Configurations  
Protection  
Communications  
Menu  
Menu  
Menu  
Front Panel Display indicators  
External Voltage  
Programming  
External Current  
Programming  
Voltage Display + ‘V’ Symbol  
(16 Segment)  
Operation  
Mode  
Current Display + ‘A’ Symbol  
(16 Segment)  
AUTO-start  
SAFE-start  
Indicator  
FOLDback  
Voltage  
Power Supply Remote Communication Active,  
Address &  
RS232/485, USB, LAN, OPT  
(GPIB, Anybus, etc…)  
Current  
Power Indicator  
Active  
Memory–Cell  
(Sequence)  
Indicator  
LFP (Locked Front Panel)  
TRIGger  
System Active  
6
G, GSP & GSPL Series  
OUT (LED)  
REM (LED)  
Blank Front Panel (ATE version)  
POWER (LED)  
2
3
1
A Blank Front Panel is available for applications where the front panel display and controls are not required and  
only remote interface (Digital/Analog) is needed.  
The Blank Front Panel option has all the standard product functions and features except the display.  
The power supply can be controlled via the rear panel Remote digital interface  
(LAN, USB, RS-232/RS-485) or via the remote Isolated Analog interface.  
Standard Unit - zero stacked up to 30 units  
Parallel and Series Configurations  
Parallel operation - Master/Slave:  
Auto paralleling Scalable Master-Slave Operation.  
Active current sharing allows up to thirty (30) identical units  
to be connected  
Total real current is programmed measured and reported by  
the Master. Up to thirty (30) power supplies operate as one.  
Standard & Blank - zero stacked up to 30 units  
Series operation  
Two units may be connected in series to increase the output voltage  
or to provide bipolar output. (Max 600V to Chassis Ground).  
Multi-Drop Remote Programming via Communication Interface  
Standard Built-in LAN, USB, RS-232 & RS-485 allows "Multi-Drop" daisy-chain control of up to 31 Power supplies  
on the same communication bus. Can be Daisy chained via built-in RS-485 Interface.  
First unit is LAN, USB, RS-232, RS-485, etc.  
All other units use RS-485 daisy chain with linking cable.  
RS-485 Link  
RS-485 Link  
LAN, USB, RS-232, RS-485, IEEE, AnyBus  
7
Graphical User Interface  
Advanced "Virtual Control Panel" allows programming and monitoring unit(s) with or without front panel display.  
1. Control and monitor DC Programmable Power Supply Series (GENESYS+, GENESYS and Z+).  
2. Automatically detect power supplies connected to a PC and/or local network.  
3. Advanced Terminal, including Modbus-TCP and EtherCAT communication interfaces.  
4. Real-time Graph and Waveform creator, including pre-built functions i.e. Sine, Triangle and Square.  
5. Solar array simulation based on VOC, VMP, IMP, ISC.  
6. Advanced functions control – Slew-Rate, Internal Resistance and Constant Power.  
7. Multi-Model Monitoring and Control Panel.  
8. Individual and Global commands control.  
GUI Waveform Profile Generator  
8
How to order GSPL15kW-22.5kW - Power Supply Identification / Accessories  
G
SPL  
20  
- 750  
-
-
-
Series Name  
Output  
Voltage  
(0~20V)  
Output  
InterfaceOptions  
AC Input Options  
Accessories Options  
Front Panel Type  
Empty: standard  
Current  
3P208 (Three Phase 170~265VAC)  
3P480 (Three Phase 342~528VAC)  
M - Printed *User Manual  
(0~1125A)  
* User Manual & GUI are  
available on the website  
B: Blank Front Panel (ATE version)  
Interface Options (Factory installed)  
P/N  
LAN (  
1.5 compliant with Multi-Drop capability)- built-in  
-
-
-
-
USB 2.0 compliant with Multi-Drop capability - built-in  
RS-232/RS-485 - built-in  
Isolated Analog Program/Monitor Interface  
(5V/10V Pgm/Mon with 600V isolation) - built-in  
Isolated Analog Programming (4-20mA)  
IEEE (488.2 & SCPI compliant with Multi-Drop capability installed)  
Modbus-TCP  
IS420  
IEEE  
MDBS  
ECAT  
EtherCAT  
Models GSPL 15kW  
Model  
Voltage (VDC) Current (A) Power (kW)  
Model  
Voltage (VDC) Current (A) Power (kW)  
GSPL20-750  
GSPL30-500  
GSPL40-376  
GSPL60-250  
GSPL80-188  
GSPL100-150  
0~20V  
0~30V  
0~40V  
0~60V  
0~80V  
0~100V  
0~750  
0~500  
0~376  
0~250  
0~188  
0~150  
15  
15  
15  
15  
15  
15  
GSPL150-100  
GSPL200-75  
GSPL300-50  
GSPL600-25  
GSPL1000-15  
GSPL1500-10  
0~150V  
0~200V  
0~300V  
0~600V  
0~1000V  
0~1500V  
0~100  
0~75  
0~50  
0~25  
0~15  
0~10  
15  
15  
15  
15  
15  
15  
Models GSPL22.5kW  
Model  
Voltage (VDC) Current (A) Power (kW)  
Model  
Voltage (VDC) Current (A) Power (kW)  
GSPL20 -1125  
GSPL30-750  
GSPL40-564  
GSPL60-375  
GSPL80-282  
GSPL100-225  
0~20V  
0~30V  
0~40V  
0~60V  
0~80V  
0~100V  
0 ~1125  
0~750  
0~564  
0~375  
0~282  
0~225  
22.5  
GSPL150-150  
GSPL200 -112. 5  
GSPL300-75  
GSPL600 -37. 5  
GSPL1000-22.5  
GSPL1500-15  
0~150V  
0~200V  
0~300V  
0~600V  
0~1000V  
0~1500V  
0~150  
0 ~112. 5  
0~75  
0~37. 5  
0~22.5  
0~15  
22.5  
22.5  
22.5  
22.5  
22.5  
22.5  
22.5  
22.56  
22.5  
22.56  
22.5  
Accessories  
Accessories will be sent separately from the Power Supply packing, according to order.  
1. Serial Communication cable  
RS-232/RS-485 cable is used to connect the power supply to the Host PC.  
Mode  
RS-485  
RS-232  
PC Connector  
DB-9F  
DB-9F  
Communication Cable  
Power Supply Connector  
Shielded L=2m  
RJ-45  
Shielded L=2m  
RJ-45  
P/N  
GEN/485-9  
GEN/232-9  
2. BusParallelingcable(Includedwiththepowersupply)  
Connectors  
2013595-1 (TYCO)  
Cables  
Shielded L=11cm  
P/N  
G/P  
3. Remote Sense Connector  
Connectors  
Cables  
P/N  
Phoenix Contact.  
Wire AWG - refer to User Manual GIC 2,5 HCV/ 3-ST-7,62  
4. User Manual  
Printed User Manual  
G/M  
9
GSPL 15kW Series Specifications  
Unless otherwise noted, specifications are warranted over the ambient temperature range of 0° to 50° Celsius.  
OUTPUT RATING  
20-750  
20  
750  
30-500  
30  
500  
40-376  
40  
376  
60-250  
60  
250  
80-188  
80  
188  
100-150 150-100  
200-75  
200  
75  
300-50  
300  
50  
600-25  
600  
25  
1000-15 1500-10  
1.Rated output voltage (*1)  
2.Rated output current (*2)  
3.Rated output power  
V
A
W
V
A
100  
150  
150  
100  
1000  
15  
1500  
10  
kW  
15000  
15000  
15040  
15000  
15040  
15000  
15000  
15000  
15000  
15000  
15000  
15000  
INPUT CHARACTERISTICS  
V
20  
30  
40  
60  
80  
100  
150  
200  
300  
600  
1000  
1500  
3-Phase, 200V models: 170~265Vac, 47~63Hz (Covers 200/230Vac).  
3-Phase, 480V models: 342~528Vac, 47~63Hz (Covers 380/400/415/440/460/480Vac).  
1.Input voltage/freq. 3 phase, 3 wire+ground (*4)  
3-Phase, 200V  
---  
51A @ 200Vac.  
models:  
2.Maximum Input current at  
---  
100% load  
3-Phase, 480V  
models:  
27A @ 380Vac.  
3.Power Factor (Typ.)  
4.Efficiency (Typ.) (*5) (*3)  
5.Inrush current (*6)  
---  
%
---  
0.94 @ 200/380Vac, rated output power.  
91  
91  
91  
91  
91  
80  
91  
91  
91  
91  
92  
92  
92  
Less than 130A.  
CONSTANT VOLTAGE MODE  
1.Max. Line regulation (*7)  
2.Max. Load regulation (*8)  
3.Ripple and noise (p-p, 20MHz) (*9)  
4.Ripple r.m.s. 5Hz~1MHz (*9)  
5.Temperature coefficient  
6.Temperature stability  
7.Warm-up drift  
8.Remote sense compensation/wire (*10)  
9.Up-prog. response time (*11)  
V
---  
---  
mV  
mV  
---  
---  
---  
V
20  
30  
40  
60  
100  
150  
200  
300  
600  
1000  
1500  
0.01% of rated output voltage.  
0.01% of rated output voltage +5mV.  
80  
10  
80  
10  
80  
10  
80  
12  
90  
15  
90  
15  
150  
20  
250  
45  
250  
60  
450  
100  
1400  
400  
1700  
600  
50PPM/°C from rated output voltage, following 30 minutes warm-up.  
0.01% of rated Vout over 8hrs. interval following 30 minutes warm-up. Constant line, load & temperature.  
Less than 0.05% of rated output voltage +2mV over 30 minutes following power on.  
2
5
50  
100  
2500  
mS  
30  
50  
30  
80  
30  
80  
50  
80  
50  
100  
1000  
50  
100  
1500  
50  
100  
2500  
50  
100  
3000  
100  
100  
3000  
150  
100  
3000  
200  
100  
3000  
Full load (*12)  
No load (*12)  
10.Down-prog. response time  
mS  
---  
600  
600  
1000  
1000  
Time for output voltage to recover within 1% of its rated output for 20~30V; 0.5% of its rated output for 40~1500V, for a load change  
10~90% of rated output current Local sense.  
11.Transient response time  
Output set point: 10~100%.  
Less than 1mS for models up to and including 100V. 2mS for models above 100V.  
12. Hold-up time  
13.Start-up delay  
---  
---  
Less than 7Sec.  
5mS Typical. Rated output power.  
CONSTANT CURRENT MODE  
1.Max. Line regulation (*7)  
2.Max. Load regulation (*13)  
3.Ripple r.m.s. 5Hz~1MHz (*14)  
V
---  
---  
20  
30  
40  
60  
80  
100  
150  
200  
300  
600  
1000  
1500  
0.05% of rated output current.  
0.08% of rated output current.  
≤1800  
20V~100V models: 100PPM/°C from rated output current, following 30 minutes warm-up.  
150V~1500V models: 70PPM/°C from rated output current, following 30 minutes warm-up.  
0.01% of rated Iout over 8hrs. interval following 30 minutes warm-up. Constant line, load & temperature.  
20V~100V models: Less than +/-0.25% of rated output current over 30 minutes following power on.  
150V~1500V models: Less than +/-0.15% of rated output current over 30 minutes following power on.  
mA  
≤1000  
≤600  
≤300  
≤200  
≤140  
≤90  
≤40  
≤30  
≤28  
≤20  
≤20  
4.Temperature coefficient  
5.Temperature stability  
6.Warm-up drift  
---  
---  
---  
ANALOG PROGRAMMING AND MONITORING (ISOLATED FROM THE OUTPUT)  
1.Vout voltage programming  
2.Iout voltage programming (*15)  
3.Vout resistor programming  
4.Iout resistor programming (*15)  
5.Output voltage monitor  
---  
---  
---  
---  
---  
---  
0~100%, 0~5V or 0~10V, user selectable. Accuracy and linearity: +/-0.15% of rated Vout.  
0~100%, 0~5V or 0~10V, user selectable. Accuracy and linearity: +/-0.4% of rated Iout.  
0~100%, 0~5/10KΩ full scale, user selectable. Accuracy and linearity: +/-0.5% of rated Vout.  
0~100%, 0~5/10KΩ full scale, user selectable. Accuracy and linearity: +/-0.5% of rated Iout.  
0~5V or 0~10V, user selectable. Accuracy: +/-0.5% of rated Vout.  
6.Output current monitor (*15)  
0~5V or 0~10V, user selectable. Accuracy: +/-0.5% of rated Iout.  
SIGNALS AND CONTROLS (ISOLATED FROM THE OUTPUT)  
Power supply output monitor. Open collector. Output On: On. Output Off: Off.  
Maximum Voltage: 30V. Maximum Sink Current: 10mA.  
1.Power supply OK #1 signal  
---  
---  
---  
---  
---  
---  
---  
CV/CC Monitor. Open collector. CC mode: On. CV mode: Off. Maximum Voltage: 30V.  
Maximum Sink Current: 10mA.  
2.CV/CC signal  
Enable/Disable analog programming control by electrical signal or dry contact.  
Remote: 0~0.6V or short. Local: 2~30V or open.  
3.LOCAL/REMOTE Analog control  
4.LOCAL/REMOTE Analog signal  
5.ENABLE/DISABLE signal  
6.INTERLOCK (ILC) control  
7.Programmed signals  
Analog programming control monitor signal. Open collector. Remote: On. Local: Off.  
Maximum Voltage: 30V. Maximum Sink Current: 10mA.  
Enable/Disable PS output by electrical signal or dry contact.  
0~0.6V or short, 2~30V or open. User selectable logic.  
Enable/Disable PS output by electrical signal or dry contact.  
Output ON: 0~0.6V or short. Output OFF: 2~30V or open.  
Two open drain programmable signals. Maximum voltage 25V. Maximum sink current 100mA  
(shunted by 27V zener).  
Maximum low level input voltage = 0.8V. Minimum high level input voltage = 2.5V.  
Maximum high level input = 5V positive edge trigger: tw = 10us minimum. Tr,Tf = 1us maximum.  
Min delay between 2 pulses 1ms.  
8.TRIGGER IN / TRIGGER OUT signals  
---  
9.DAISY_IN/SO control signal  
10.DAISY_OUT/PS_OK #2 signal  
---  
---  
By electrical Voltage: 0~0.6V/2~30V or dry contact.  
4~5V = OK, 0V (500Ω impedance) = Fail.  
FUNCTIONS AND FEATURES  
1.Parallel operation  
2.Series operation  
3.Daisy chain  
4.Constant power control  
5.Output resistance control  
---  
---  
---  
---  
---  
Possible. Up to 4 identical units in Master/Slave mode. Refer to instruction manual.  
Possible. Two identical units. Refer to instruction manual.  
Power supplies can be connected in Daisy chain to synchronize their turn-on and turn-off.  
Limits the output power to a programmed value. Programming via the communication ports or the front panel.  
Emulates series resistance. Resistance range: 1~1000mΩ. Programming via communication ports or front panel.  
Programmable Output rise and Output fall slew rate.  
Programming range: 0.0001~999.99 V/mS. or A/mS.  
Programming via communication ports or front panel.  
6.Slew rate control  
---  
10  
PROGRAMMING AND READBACK (USB, LAN, RS232/485, Optional (*17) (*18) Interfaces)  
PROGRAMMING AND READBACK (USB, LAN, RS232/485, Optional (*17) (*20) Interfaces)  
V
20  
30  
40  
60  
80  
100  
150  
200  
300  
600  
1000  
1500  
1.Vout programming accuracy (*16)  
2.Iout programming accuracy (*15)  
3.Vout programming resolution  
4.Iout programming resolution  
5.Vout readback accuracy  
---  
---  
---  
---  
---  
---  
0.05% of rated output voltage.  
0.1% of actual output current +0.2% of rated output current.  
0.002% of rated output voltage.  
0.002% of rated output current.  
0.1% of rated output voltage.  
6.Iout readback accuracy (*15)  
0.2% of rated output current.  
% of rated  
7.Vout readback resolution  
8.Iout readback resolution  
0.006%  
0.002%  
0.004%  
0.003%  
0.004%  
0.004%  
0.003%  
0.005%  
0.002%  
0.006%  
0.011%  
0.008%  
0.008%  
0.011%  
0.006%  
0.002%  
0.004%  
0.003%  
0.003%  
0.005%  
0.011%  
0.008%  
0.008%  
0.011%  
output voltage  
% of rated  
output current  
Profiles of up to 100 steps can be stored in 4 memory cells.  
Activation by command via communication ports or front panel.  
% of rated  
output  
7.Arbitrary waveforms  
PROTECTIVE FUNCTIONS  
1.Foldback protection  
V
20  
30  
40  
60  
80  
100  
150  
200  
300  
600  
1000  
1500  
Output shut-down when power supply changes mode from CV or Power Limit to CC mode or from CC or Power Limit to CV mode. User  
presetable. Reset by AC input recycle in autostart mode, by Power Switch, by OUTPUT button, by rear panel or by communication.  
---  
2.Over-voltage protection (OVP)  
3.Over-voltage programming range  
4.Over-voltage programming accuracy  
5.Output under voltage limit (UVL)  
---  
V
---  
Output shut-down. Reset by AC input recycle in autostart mode, by Power Switch, by OUTPUT button, by rear panel or by communication.  
1~24  
2~36  
2~44.1  
5~66.15  
5~88.2 5~110.25 5~165.37 5~220.5 5~330.75 5~661.5 5~1212.75 5~1653.75  
+/-1% of rated output voltage.  
Prevents from adjusting Vout below limit. Does not apply in analog programming.  
Preset by front panel or communication port.  
Shuts down the output. Auto recovery by autostart mode.  
Prevents adjustment of Vout below limit. P.S output turns Off during under voltage condition.  
Reset by AC input recycle in autostart mode, by Power Switch, by OUTPUT button, by rear panel or by communication.  
---  
---  
---  
6.Over temperature protection  
7.Output under voltage protection (UVP)  
FRONT PANEL  
---  
---  
---  
---  
---  
---  
---  
---  
---  
1.Control functions  
Multiple options with 2 Encoders.  
Vout/Iout/Power Limit manual adjust.  
OVP/UVL/UVP manual adjust.  
Protection Functions - OVP, UVL, UVP, Foldback, OCL, ENA, ILC.  
Communication Functions - Selection of LAN, RS232, RS485, USB or Optional communication interface.  
Output ON/OFF. Front Panel Lock.  
Communication Functions - Selection of Baud Rate, Address, IP and communication language.  
Analog Control Functions - Selection Voltage/resistive programming 5V/10V, 5KΩ/10KΩ programming.  
Analog Monitor Functions - Selection of Voltage/Current Monitoring 5V/10V.  
Vout: 4 digits, accuracy: 0.05% of rated output voltage +/-1 count.  
2.Display  
---  
Iout: 4 digits, accuracy: 0.2% of rated output current +/-1 count.  
3.Front Panel Buttons Indications  
4.Front Panel Display Indications  
---  
---  
OUTPUT ON, ALARM, PREVIEW, FINE, COMMUNICATION, PROTECTION, CONFIGURATION, SYSTEM, SEQUENCER.  
Voltage, Current, Power, CV, CC, CP, External Voltage, External Current, Address, LFP Autostart, Safetstart, Foldback V/I, Remote  
(communication), RS/USB/LAN/Optional communication interface, Trigger, Load/Store Cell.  
ENVIRONMENTAL CONDITIONS  
1.Operating temperature  
0~50°C, 100% load.  
---  
---  
---  
---  
2.Storage temperature  
3.Operating humidity  
4.Storage humidity  
5.Altitude (*17)  
-30~85°C.  
20~90% RH (no condensation).  
10~95% RH (no condensation).  
Operating: 10000ft (3000m), output current derating 2%/100m or Ta derating 1°C/100m above 1500m.  
Non-operating: 40000ft (12000m).  
---  
MECHANICAL  
1.Cooling  
2.Weight  
Forced air cooling by internal fans. Airflow direction: From front panel to power supply rear.  
Less than 18.  
---  
Kg  
W: 423, H: 88.0, D: 594.6. Refer to outline drawing.  
MIL-810G, method 514.6, Procedure I, test condition Annex C - 2.1.3.1  
Less than 20G, half sine, 11mS. Unit is unpacked.  
3.Dimensions (WxHxD)  
4.Vibration  
5.Shock  
mm  
---  
---  
SAFETY/EMC  
1.Safety standards  
1.1.Interface classification  
---  
---  
UL61010-1, CSA22.2 No.61010-1, IEC61010-1, EN61010-1.  
Vout≤50V Models: Output, J1, J2, J3, J4, J5, J6, J7, J8 (sense) & J9 (communication options) are Non Hazardous.  
60≤Vout≤1500V Models: Output & J8 (sense) are hazardous, J1, J2, J3, J4, J5, J6, J7 & J9 (communication options) are Non Hazardous.  
Vout≤50V Models: Input – Output & J8 (sense), J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 4242VDC 1min,  
1.2.Withstand voltage  
Input - Ground: 2835VDC 1min.  
60V≤Vout≤100V Models: Input – Output & J8 (sense), J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 4242VDC 1min,  
Output & J8 (sense) - J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 850VDC 1min, Output & J8 (sense) - Ground: 1500VDC 1min,  
Input - Ground: 2835VDC 1min.  
---  
100V<Vout≤600V Models: Input – Output & J8 (sense), J1, J2, J3, J4, J5, J6, J7 and J9 (communication options): 4242VDC 1min,  
Output & J8 (sense) - J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 1275VDC 1min, Output & J8 (sense) - Ground: 2500VDC 1min.  
Input - Ground: 2835VDC 1min.  
1000V<Vout≤1500V Models: Input – Output & J8 (sense), J1, J2, J3, J4, J5, J6, J7 and J9 (communication options): 4000VDC 1min,  
Output & J8 (sense) - J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 2000VDC 1min, Output & J8 (sense) - Ground: 3280VDC 1min.  
Input - Ground: 2835VDC 1min.  
1.3.Isolation resistance  
2.EMC standards (*18)  
2.1.Conducted emission  
2.2.Radiated emission  
---  
---  
---  
---  
>60Mohm at 25°C, 70%RH, Output to Ground 500VDC.  
IEC/EN61204-3 Industrial environment.  
IEC/EN61204-3 Industrial environment, Annex H table H.1, FCC Part 15-A, VCCI-A.  
IEC/EN61204-3 Industrial environment, Annex H table H.3 and H.4, FCC Part 15-A, VCCI-A.  
NOTES:  
*1: Minimum voltage is guaranteed to maximum 0.15% of rated output voltage for 20V and 30V models; 0.1% of rated output voltage for 40V~1500V models.  
*2: Minimum current is guaranteed to maximum 0.2% of rated output current.  
*3: Typ. at Ta=25°C, rated output power.  
*4: For cases where conformance to various safety standards (UL, IEC, etc…) is required, to be described as 190-240Vac (50/60Hz) for 3-Phase 200V models and 380~480Vac (50/60Hz) for 3-Phase 480V models.  
*5: 3-Phase 200V models: At 200Vac input voltage, 3-Phase 480V: At 380Vac input voltage. With rated output power.  
*6: Not including EMI filter inrush current, less than 0.2mS.  
*7: 3-Phase 200V models: 170~265Vac, 3-Phase 480V models:342~528Vac. Constant load.  
*8: From No-Load to Full-Load, constant input voltage. Measured at the sensing point in Remote Sense.  
*9: For 20V~150V models: Measured with JEITA RC-9131C (1:1) probe. For 200~1500V models: Measured with 100:1 probe.  
*10: The maximum voltage on the power supply terminals must not exceed the rated voltage.  
*11: From 10% to 90% of Rated Output Voltage at rated resistive load.  
*12: From 90% to 10% of Rated Output Voltage.  
*13: For load voltage change, equal to the unit voltage rating, constant input voltage.  
*14: The ripple is measured at 10~100% of rated output voltage and rated output current. B.W 5Hz~1MHz.  
*15: The Constant Current programming, readback and monitoring accuracy do not include the warm-up and Load regulation thermal drift.  
*16: Measured at the sensing point.  
*17: Max. ambient temperature for IEEE is 40°C.  
*18: Signal and control ports interface cables length: Less than 3m, DC output power port cables length: Less than 30m.  
11  
Outline Drawing  
GSPL15kW  
5.9 ±0.5  
76.2 ±0.5  
19 ±0.5  
50 ±0.5  
+
-
0.7  
0.3  
88  
21.5 ±1.0  
44.45 ±1.0  
3x 21 ±1.0  
3x 44.45 ±1.0  
21.5 ±1.0  
44.45 ±1.0  
12  
Outline Drawing  
GSPL15kW  
4 4 . 4 5 ± 1 . 0  
2 1 . 5 ± 1 . 0  
3 x 4 4 . 4 5 ± 1 . 0  
3 x 2 1 ± 1 . 0  
4 4 . 4 5 ± 1 . 0  
2 1 . 5 ± 1 . 0  
0 - . 3 8 8  
0 . + 7  
5 0 ± 0 . 5  
1 9 ± 0 . 5  
7 6 . 2 ± 0 . 5  
5 . 9 ± 0 . 5  
13  
GSPL 22.5kW Series Specifications  
Unless otherwise noted, specifications are warranted over the ambient temperature range of 0° to 50° Celsius.  
OUTPUT RATING  
20 -1125  
30-750  
40-564  
60-375  
80-282  
100-225  
150-150 200 -112.5 300-75  
600-37.5 1000-22.5 1500-15  
1.Rated output voltage (*1)  
2.Rated output current (*2)  
3.Rated output power  
V
A
W
20  
1125  
22500  
30  
750  
22500  
40  
564  
22560  
60  
375  
22500  
80  
282  
22560  
100  
225  
22500  
150  
150  
22500  
200  
112.5  
22500  
300  
75  
22500  
600  
37.5  
22500  
1000  
22.5  
22500  
1500  
15  
22500  
INPUT CHARACTERISTICS  
1.Input voltage/freq. 3 phase, 3 wire+ground (*4)  
V
20  
30  
40  
60  
80  
100  
150  
200  
300  
600  
1000  
1500  
3-Phase, 200V models: 170~265Vac, 47~63Hz (Covers 200/230Vac).  
---  
3-Phase, 480V models: 342~528Vac, 47~63Hz (Covers 380/400/415/440/460/480Vac).  
2.Maximum Input current at 3-Phase, 200V models:  
75.5A @ 200Vac.  
40.5A @ 380Vac.  
0.94 @ 200/380Vac, rated output power.  
100% load  
3-Phase, 480V models:  
---  
---  
%
3.Power Factor (Typ.)  
4.Efficiency (Typ.) (*5) (*3)  
5.Inrush current (*6)  
91  
91  
91  
91  
91  
80  
91  
91  
91  
92  
92  
92  
92  
---  
Less than 195A.  
CONSTANT VOLTAGE MODE  
1.Max. Line regulation (*7)  
2.Max. Load regulation (*8)  
3.Ripple and noise (p-p, 20MHz) (*9)  
4.Ripple r.m.s. 5Hz~1MHz (*9)  
5.Temperature coefficient  
6.Temperature stability  
7.Warm-up drift  
8.Remote sense compensation/wire (*10)  
9.Up-prog. response time (*11)  
10.Down-prog. response time  
V
30  
40  
60  
100  
150  
200  
300  
600  
1000  
1500  
20  
---  
---  
mV  
mV  
---  
---  
---  
V
0.01% of rated output voltage.  
0.01% of rated output voltage +5mV.  
80  
10  
80  
10  
80  
12  
90  
15  
90  
15  
150  
20  
250  
45  
250  
60  
450  
100  
2000  
550  
2500  
700  
80  
10  
50PPM/°C from rated output voltage, following 30 minutes warm-up.  
0.01% of rated Vout over 8hrs. interval following 30 minutes warm-up. Constant line, load & temperature.  
Less than 0.05% of rated output voltage +2mV over 30 minutes following power on.  
5
50  
100  
2500  
2
30  
50  
600  
mS  
mS  
30  
80  
600  
30  
80  
1000  
50  
80  
1000  
50  
100  
1000  
50  
100  
1500  
50  
100  
2500  
50  
100  
3000  
100  
100  
3000  
150  
100  
3000  
200  
100  
3000  
Full load (*12)  
No load (*12)  
11.Transient response time  
Time for output voltage to recover within 1% of its rated output for 20~30V; 0.5% of its rated output for 40~1500V, for a load change  
10~90% of rated output current Local sense.  
---  
Output set point: 10~100%.  
Less than 1mS for models up to and including 100V. 2mS for models above 100V.  
12.Start-up delay  
13.Hold-up time  
---  
---  
Less than 7Sec.  
5mS Typical. Rated output power.  
CONSTANT CURRENT MODE  
1.Max. Line regulation (*7)  
2.Max. Load regulation (*13)  
3.Ripple r.m.s. 5Hz~1MHz (*14)  
4.Temperature coefficient  
V
---  
---  
mA  
20  
30  
40  
60  
80  
100  
150  
200  
≤60  
300  
≤45  
600  
≤42  
1000  
≤25  
1500  
≤25  
0.05% of rated output current.  
0.08% of rated output current.  
≤2700  
20V~100V models: 100PPM/°C from rated output current, following 30 minutes warm-up.  
150V~1500V models: 70PPM/°C from rated output current, following 30 minutes warm-up.  
0.01% of rated Iout over 8hrs. interval following 30 minutes warm-up. Constant line, load & temperature.  
20V~100V models: Less than +/-0.25% of rated output current over 30 minutes following power on.  
150V~1500V models: Less than +/-0.15% of rated output current over 30 minutes following power on.  
≤1500  
≤900  
≤450  
≤300  
≤210  
≤135  
---  
---  
---  
5.Temperature stability  
6.Warm-up drift  
ANALOG PROGRAMMING AND MONITORING (ISOLATED FROM THE OUTPUT)  
1.Vout voltage programming  
2.Iout voltage programming (*15)  
3.Vout resistor programming  
4.Iout resistor programming (*15)  
5.Output voltage monitor  
---  
---  
---  
---  
---  
---  
0~100%, 0~5V or 0~10V, user selectable. Accuracy and linearity: +/-0.15% of rated Vout.  
0~100%, 0~5V or 0~10V, user selectable. Accuracy and linearity: +/-0.4% of rated Iout.  
0~100%, 0~5/10KΩ full scale, user selectable. Accuracy and linearity: +/-0.5% of rated Vout.  
0~100%, 0~5/10KΩ full scale, user selectable. Accuracy and linearity: +/-0.5% of rated Iout.  
0~5V or 0~10V, user selectable. Accuracy: +/-0.5% of rated Vout.  
6.Output current monitor (*15)  
0~5V or 0~10V, user selectable. Accuracy: +/-0.5% of rated Iout.  
SIGNALS AND CONTROLS (ISOLATED FROM THE OUTPUT)  
1.Power supply OK #1 signal  
---  
---  
---  
---  
---  
---  
---  
Power supply output monitor. Open collector. Output On: On. Output Off: Off.  
Maximum Voltage: 30V. Maximum Sink Current: 10mA.  
CV/CC Monitor. Open collector. CC mode: On. CV mode: Off. Maximum Voltage: 30V.  
Maximum Sink Current: 10mA.  
Enable/Disable analog programming control by electrical signal or dry contact.  
Remote: 0~0.6V or short. Local: 2~30V or open.  
Analog programming control monitor signal. Open collector. Remote: On. Local: Off.  
Maximum Voltage: 30V. Maximum Sink Current: 10mA.  
Enable/Disable PS output by electrical signal or dry contact.  
0~0.6V or short, 2~30V or open. User selectable logic.  
Enable/Disable PS output by electrical signal or dry contact.  
Output ON: 0~0.6V or short. Output OFF: 2~30V or open.  
Two open drain programmable signals. Maximum voltage 25V. Maximum sink current 100mA  
(shunted by 27V zener).  
2.CV/CC signal  
3.LOCAL/REMOTE Analog control  
4.LOCAL/REMOTE Analog signal  
5.ENABLE/DISABLE signal  
6.INTERLOCK (ILC) control  
7.Programmed signals  
8.TRIGGER IN / TRIGGER OUT signals  
Maximum low level input voltage = 0.8V. Minimum high level input voltage = 2.5V.  
Maximum high level input = 5V positive edge trigger: tw = 10us minimum. Tr,Tf = 1us maximum.  
Min delay between 2 pulses 1ms.  
---  
9.DAISY_IN/SO control signal  
10.DAISY_OUT/PS_OK #2 signal  
---  
---  
By electrical Voltage: 0~0.6V/2~30V or dry contact.  
4~5V = OK, 0V (500Ω impedance) = Fail.  
FUNCTIONS AND FEATURES  
1.Parallel operation  
2.Series operation  
---  
---  
---  
---  
---  
Possible. Up to 4 identical units in Master/Slave mode. Refer to instruction manual.  
Possible. Two identical units. Refer to instruction manual.  
Power supplies can be connected in Daisy chain to synchronize their turn-on and turn-off.  
Limits the output power to a programmed value. Programming via the communication ports or the front panel.  
Emulates series resistance. Resistance range: 1~1000mΩ. Programming via communication ports or front panel.  
Programmable Output rise and Output fall slew rate.  
Programming range: 0.0001~999.99 V/mS. or A/mS.  
Programming via communication ports or front panel.  
3.Daisy chain  
4.Constant power control  
5.Output resistance control  
6.Slew rate control  
---  
---  
7.Arbitrary waveforms  
Profiles of up to 100 steps can be stored in 4 memory cells.  
Activation by command via communication ports or front panel.  
14  
PROGRAMMING AND READBACK (USB, LAN, RS232/485, Optional (*17) (*20) Interfaces)  
V
20  
30  
40  
60  
80  
100  
150  
200  
300  
600  
1000  
1500  
1.Vout programming accuracy (*16)  
2.Iout programming accuracy (*15)  
3.Vout programming resolution  
4.Iout programming resolution  
5.Vout readback accuracy  
---  
---  
---  
---  
---  
---  
0.05% of rated output voltage.  
0.1% of actual output current +0.2% of rated output current.  
0.002% of rated output voltage.  
0.002% of rated output current.  
0.1% of rated output voltage.  
6.Iout readback accuracy (*15)  
0.2% of rated output current.  
% of rated  
7.Vout readback resolution  
8.Iout readback resolution  
0.006%  
0.01%  
0.004%  
0.002%  
0.004%  
0.003%  
0.003%  
0.004%  
0.002%  
0.005%  
0.011%  
0.005%  
0.008%  
0.008%  
0.006%  
0.01%  
0.004%  
0.002%  
0.003%  
0.004%  
0.011%  
0.005%  
0.008%  
0.008%  
output voltage  
% of rated  
outputcurrent  
PROTECTIVE FUNCTIONS  
1.Foldback protection  
V
20  
30  
40  
60  
80  
100  
150  
200  
300  
600  
1000  
1500  
Output shut-down when power supply changes mode from CV or Power Limit to CC mode or from CC or Power Limit to CV mode. User  
presetable. Reset by AC input recycle in autostart mode, by Power Switch, by OUTPUT button, by rear panel or by communication.  
---  
2.Over-voltage protection (OVP)  
3.Over-voltage programming range  
4.Over-voltage programming accuracy  
5.Output under voltage limit (UVL)  
Output shut-down. Reset by AC input recycle in autostart mode, by Power Switch, by OUTPUT button, by rear panel or by communication.  
---  
V
---  
1~24  
2~36  
2~44.1  
5~66.15  
5~88.2  
5~110.25 5~165.37 5~220.5 5~330.75 5~661.5 5~1212.75 5~1653.75  
+/-1% of rated output voltage.  
Prevents from adjusting Vout below limit. Does not apply in analog programming.  
Preset by front panel or communication port.  
Shuts down the output. Auto recovery by autostart mode.  
Prevents adjustment of Vout below limit. P.S output turns Off during under voltage condition.  
Reset by AC input recycle in autostart mode, by Power Switch, by OUTPUT button, by rear panel or by communication.  
---  
---  
---  
6.Over temperature protection  
7.Output under voltage protection (UVP)  
FRONT PANEL  
1.Control functions  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
Multiple options with 2 Encoders.  
Vout/Iout/Power Limit manual adjust.  
OVP/UVL/UVP manual adjust.  
Protection Functions - OVP, UVL, UVP, Foldback, OCL, ENA, ILC.  
Communication Functions - Selection of LAN, RS232, RS485, USB or Optional communication interface.  
Output ON/OFF. Front Panel Lock.  
Communication Functions - Selection of Baud Rate, Address, IP and communication language.  
Analog Control Functions - Selection Voltage/resistive programming 5V/10V, 5KΩ/10KΩ programming.  
Analog Monitor Functions - Selection of Voltage/Current Monitoring 5V/10V.  
Vout: 4 digits, accuracy: 0.05% of rated output voltage +/-1 count.  
Iout: 4 digits, accuracy: 0.2% of rated output current +/-1 count.  
OUTPUT ON, ALARM, PREVIEW, FINE, COMMUNICATION, PROTECTION, CONFIGURATION, SYSTEM, SEQUENCER.  
2.Display  
3.Front Panel Buttons Indications  
4.Front Panel Display Indications  
Voltage, Current, Power, CV, CC, CP, External Voltage, External Current, Address, LFP Autostart, Safetstart, Foldback V/I, Remote  
(communication), RS/USB/LAN/Optional communication interface, Trigger, Load/Store Cell.  
---  
ENVIRONMENTAL CONDITIONS  
1.Operating temperature  
2.Storage temperature  
3.Operating humidity  
4.Storage humidity  
---  
---  
---  
---  
0~50°C, 100% load.  
-30~85°C.  
20~90% RH (no condensation).  
10~95% RH (no condensation).  
5.Altitude (*17)  
Operating: 10000ft (3000m), output current derating 2%/100m or Ta derating 1°C/100m above 1500m.  
Non-operating: 40000ft (12000m).  
---  
MECHANICAL  
1.Cooling  
2.Weight  
---  
Kg  
Forced air cooling by internal fans. Airflow direction: From front panel to power supply rear.  
Less than 25.  
3.Dimensions (WxHxD)  
4.Vibration  
5.Shock  
W: 423, H: 132.5, D: 628.5. Refer to outline drawing.  
MIL-810G, method 514.6, Procedure I, test condition Annex C - 2.1.3.1  
Less than 20G, half sine, 11mS. Unit is unpacked.  
mm  
---  
---  
SAFETY/EMC  
1.Safety standards  
1.1.Interface classification  
---  
---  
UL61010-1, CSA22.2 No.61010-1, IEC61010-1, EN61010-1.  
Vout≤50V Models: Output, J1, J2, J3, J4, J5, J6, J7, J8 (sense) & J9 (communication options) are Non Hazardous.  
60≤Vout≤1500V Models: Output & J8 (sense) are hazardous, J1, J2, J3, J4, J5, J6, J7 & J9 (communication options) are Non Hazardous.  
1.2.Withstand voltage  
Vout≤50V Models: Input – Output & J8 (sense), J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 4242VDC 1min,  
Input - Ground: 2835VDC 1min.  
60V≤Vout≤100V Models: Input – Output & J8 (sense), J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 4242VDC 1min,  
Output & J8 (sense) - J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 850VDC 1min, Output & J8 (sense) - Ground: 1500VDC 1min,  
Input - Ground: 2835VDC 1min.  
100V<Vout≤600V Models: Input – Output & J8 (sense), J1, J2, J3, J4, J5, J6, J7 and J9 (communication options): 4242VDC 1min,  
Output & J8 (sense) - J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 1275VDC 1min, Output & J8 (sense) - Ground: 2500VDC 1min.  
Input - Ground: 2835VDC 1min.  
---  
1000V<Vout≤1500V Models: Input – Output & J8 (sense), J1, J2, J3, J4, J5, J6, J7 and J9 (communication options): 4000VDC 1min,  
Output & J8 (sense) - J1, J2, J3, J4, J5, J6, J7 & J9 (communication options): 2000VDC 1min, Output & J8 (sense) - Ground: 3280VDC 1min.  
Input - Ground: 2835VDC 1min.  
1.3.Isolation resistance  
2.EMC standards (*18)  
2.1.Conducted emission  
2.2.Radiated emission  
---  
---  
---  
---  
>60Mohm at 25°C, 70%RH, Output to Ground 500VDC.  
IEC/EN61204-3 Industrial environment.  
IEC/EN61204-3 Industrial environment, Annex H table H.1, FCC Part 15-A, VCCI-A.  
IEC/EN61204-3 Industrial environment, Annex H table H.3 and H.4, FCC Part 15-A, VCCI-A.  
NOTES:  
**: Coming soon  
*1: Minimum voltage is guaranteed to maximum 0.15% of rated output voltage for 20V and 30V models; 0.1% of rated output voltage for 40V~1500V models.  
*2: Minimum current is guaranteed to maximum 0.2% of rated output current.  
*3 Typ. at Ta=25°C, rated output power.  
*4: For cases where conformance to various safety standards (UL, IEC, etc…) is required, to be described as 190-240Vac (50/60Hz) for 3-Phase 200V models  
and 380~480Vac (50/60Hz) for 3-Phase 480V models.  
*5: 3-Phase 200V models: At 200Vac input voltage, 3-Phase 480V: At 380Vac input voltage. With rated output power.  
*6: Not including EMI filter inrush current, less than 0.2mS.  
*7: 3-Phase 200V models: 170~265Vac, 3-Phase 480V models: 342~528Vac. Constant load.  
*8: From No-Load to Full-Load, constant input voltage. Measured at the sensing point in Remote Sense.  
*9: For 20V~150V models: Measured with JEITA RC-9131C (1:1) probe. For 200~1500V models: Measured with 100:1 probe.  
*10: The maximum voltage on the power supply terminals must not exceed the rated voltage.  
*11: From 10% to 90% of Rated Output Voltage at rated resistive load.  
*12: From 90% to 10% of Rated Output Voltage.  
*13: For load voltage change, equal to the unit voltage rating, constant input voltage.  
*14:The ripple is measured at 10~100% of rated output voltage and rated output current. B.W 5Hz~1MHz.  
*15: The Constant Current programming, readback and monitoring accuracy do not include the warm-up and Load regulation thermal drift.  
*16: Measured at the sensing point.  
*17 Max. ambient temperature for IEEE is 40°C.  
*18: Signal and control ports interface cables length: Less than 3m, DC output power port cables length: Less than 30m.  
15  
Outline Drawing  
GSPL22.5kW  
37.7 ±0.5  
57.1 ±0.5  
16.25 ±0.5  
100 ±0.5  
+
-
0.7  
0.3  
132.5  
21.5 ±1.0  
2X 44.5 ±1.0  
3x 65.5 ±1.0  
21.5 1.0  
2X 44.45 1.0  
16  
Outline Drawing  
GSPL22.5kW  
2 X 4 4 . 4 5 ± 1 . 0  
2 1 . 5 ± 1 . 0  
3 x 6 5 . 4 5 ± 1 . 0  
2 X 4 4 . 4 5 ± 1 . 0  
2 1 . 5 ± 1 . 0  
0 - . 3  
0 . + 7  
1 3 2 . 5  
1 0 0 ± 0 . 5  
1 6 . 2 5 ± 0 . 5  
5 7 . 1 ± 0 . 5  
3 7 . 7 ± 0 . 5  
17  
Outline Drawing  
Air Filter Kit  
18  
Front Panel Air Filter Assembly  
Front panel dust cover is available for dusty air environment applications  
Dust cover is removable snap-in filter (for easy maintenance)  
• Part Number (for standard unit) : G-AFK  
• Part Number (for unit with blank front panel) : GB-AFK  
For GSP 10kW/15kW series order part number: GSP10kW-AFK / GSP15kW-AFK  
Accessories  
1. Front Panel dust filter / Field installation kit:  
Technical Specifications: Unit with Air Filter Assembly Installed  
• Derating (enviromental):  
• Operating Temperature  
• For all models (except 10V): 0 C  
• Altitude  
• For all models (except 10V): derate 2 C  
• For 10V model: derate 1 C/100m or 2% of load/100m (above 2000m)  
̊ to +40 C̊ full load; For 10V model: 0 C̊ to +30 C̊ , derate 5A/ C̊ for 30 C̊ < Ta < +40 C̊  
̊
/100m or 2% of load/100m (above 2000m)  
̊
Filter Foam Technical Specifications  
• Material: reticulated polyurethane foam  
• Thickness:3.8 mm  
• Porosity: 45ppi  
• Operating Temperature Range: 0 C  
• Storage Temperature Range: -40 C  
• Humidity: 95% RH  
̊
to +60 C  
̊
̊
to +85 C  
̊
Air Filter Assembly Components  
Standard Unit (P/N: G-AFK)  
• Air Filter Cover (two pieces)  
• Slide Button #1 (two locations: near AC ON/OFF switch and near left-hand side of front panel display)  
• Slide Button #2 (one location: right-hand side of front panel display)  
• Filter foam (two pieces)  
Blank Front Panel Unit (P/N: GB-AFK)  
• Air Filter Cover (one piece)  
• Slide Button #1 (two locations) • Filter foam (one piece)  
19  
NORTH AMERICA  
Denmark  
TDK-Lambda Americas Inc  
TDK-Lambda Nordic  
Haderslevvej 36B, DK-6000 Kolding, Denmark  
TEL: +45-8853-8086  
E-mail: info@dk.tdk-lambda.com  
www.emea.lambda.tdk.com/dk  
405 Essex Rd. Neptune, NJ 07753  
Tel: +1-732-922-9300 Fax: +1-732-922-1441  
E-mail: sales@us.tdk-lambda.com  
www.us.lambda.tdk.com  
UK  
JAPAN  
TDK-Lambda UK Ltd.  
Kingsley Avenue Ilfracombe, Devon  
EX 34 8ES, United Kingdom  
TDK-Lambda Corporation  
Nihonbashi Takashimaya Mitsui Bldg. 2-5-1 Nihonbashi,  
Chuo-ku, Tokyo 103-6128, JAPAN  
Tel: +44-1271-856666 Fax: +44-1271-864894  
E-mail: info@uk.tdk-lambda.com  
www.emea.lambda.tdk.com/uk  
TEL: +81-3-6778-1113 FAX: +81-3-6778-1160  
www.jp.lambda.tdk.com  
CHINA  
FRANCE  
TDK-Lambda (China) Electronics Co. Ltd,  
Shanghai Office 5th Floor Kehui Tower, 1188 Qinzhou Road (North),  
Xuhui District Shanghai 200233, China  
TDK-Lambda France SAS  
3 Avenue du Canada,  
Parc Technopolis - Bâtiment Sigma,  
91940 Les Ulis – France CS 41077  
Tel: +33 1 60 12 71 65 Fax: +33 1 60 12 71 66  
E-mail: france@fr.tdk-lambda.com  
www.emea.lambda.tdk.com/fr  
Tel: +86-21-6485-0777 Fax: +86-21-6485-0666  
www.lambda.tdk.com.cn  
Beijing Branch of TDK-Lambda (China) Electronic Co. Ltd.  
Room 12B11-12B12, Unit 7 Dacheng square, No.28  
Xuanwumenxi Street, Xuanwu District Beijing, 100053, CHINA  
Tel: +86-10-6310-4872 Fax: +86-10-6310-4874  
www.lambda.tdk.com.cn  
GERMANY  
TDK-Lambda Germany GmbH  
Karl-Bold-Str.40,  
D-77855 Achern, Germany  
Tel: +49-7841-666-0 Fax: +49-7841-500-0  
E-mail: info.germany@de.tdk-lambda.com  
www.emea.lambda.tdk.com/de  
Shenzhen Branch of TDK-Lambda (China) Electronics Co.Ltd.  
69/F, Ping An Finance Centre, 5033 Yitian Road,  
Futian District, Shenzhen,China  
Tel: +86-755-83588261 Fax: +86-755-83588260  
www.lambda.tdk.com.cn  
AUSTRIA  
KOREA  
TDK-Lambda Germany GmbH Austria Sales Office  
Aredstrasse 22, 2544 Leobersdorf, Austria  
Tel: +43-2256-65584 Fax: +43-2256-64512  
E-mail: info@at.tdk-lambda.com  
TDK-Lambda Corporation Korea Branch  
Seocho-Dong,12F. Songnam Bldg. 273, Gangnam Daero,  
Seocho-Gu, Seoul 06730, Republic of Korea  
Tel: +82-2-3473-7051 Fax: +82-2-3472-9137  
www.lambda.tdk.co.kr  
www.emea.lambda.tdk.com/at  
ITALY  
SINGAPORE  
TDK-Lambda France Sas Succursale Italiana  
Via Giacomo Matteotti 62,  
20092 Cinisello Balsamo (MI), Italia  
Tel: +39-02-6129-3863 Fax: +39-02-6129-0900  
E-mail: info.italia@it.tdk-lambda.com  
www.emea.lambda.tdk.com/it  
TDK-Lambda Singapore Pte.Ltd.  
Blk 1008 Toa Payoh North # 07-01/03  
Singapore 318996  
Tel: +65-6251-7211 Fax: +65-6250-9171  
www.sg.lambda.tdk.com  
INDIA  
ISRAEL  
TDK India Private Limited. Power Supply Division  
#87, The Centrum, 4th Floor, Infantry Road, Bengaluru,  
Karnataka, -560 001, INDIA  
TDK-Lambda Ltd.  
Sales Office: Alexander Yanai 1, Petah Tikva, 4927701, ISRAEL  
Tel: +972-3-9024-333 Fax: +972-3-9024-777  
Tel: +91-80-40390660 Fax: +91-80-40390603  
Plant: 56 Haharoshet St.,  
MALAYSIA  
Karmiel Industrial Zone 2165158, Israel  
Tel: +972-4-9887-491 Fax: +972- 4-9583-071  
www.emea.lambda.tdk.com/il E-mail: info@tdk-lambda.co.il  
TDK-Lambda Malaysia Sdn. Bhd. (Nilai Office)  
c/o TDK (Malaysia) Sdn. Bhd., Lot 709, Nilai Industrial Estate  
71800 Nilai, Negeri Sembilan, MALAYSIA  
Switzerland  
TEL: +60-6-797-8800 Fax: +60-6-797-8966  
TDK-Lambda Germany GmbH  
Switzerland Sales Office, Eichtalstr. 55  
8634 Hombrechtikon - Switzerland  
Tel: +41 44 850 53 53  
E-mail: info@ch.tdk-lambda.com  
www.emea.lambda.tdk.com/ch  
https://product.tdk.com/en/power  
www.emea.lambda.tdk.com