Flex Series
GF505 and GF510
5 and 10 Zone Conventional
Fire Alarm Control Panels
Description
The Flex 505 is a five zone fire alarm control panel (FACP)
and the Flex 510 is a ten zone FACP. These combination
control and digital communicator panels provide reliable
fire signaling protection for medium sized commercial,
industrial and institutional buildings.
Initiating device circuits (IDCs) for Flex Series panels are
programmable and operate in Class B (Style B). Each
panel is compatible with conventional input devices such
as two-wire smoke detectors, four-wire smoke detectors,
pull stations, water flow devices, tamper switches and
other normally-open contact devices. This includes System
GF510
Sensor i3™ Series microprocessor-based detectors with
advanced features like drift compensation, maintenance
alert and freeze warning. (See the Gamewell-FCI Device
Compatibility Document, P/N 52195, for a listing of com-
patible devices).
Features
•
IBC Seismic Certified.
•
Class B (Style B) initiating device circuits (IDCs):
- Flex 505 - five programmable IDCs
- Flex 510 - ten programmable IDCs
Built-in digital alarm communicator/transmitter (DACT).
Four Class B (Style Y) notification appliance circuits
(NACs) programmable for the following:
- ADA compliant strobe synchronization
- Selective silence (horn/strobe mute)
- Temporal or steady signal
•
•
Outputs include four notification appliance circuits (NACs),
three programmable Form-C relays (factory pre-set for
Alarm, Trouble and Supervisory), and resettable and non
resettable power (24 VDC) for special applications. NACs
are power limited and operate in Class B (Style Y). The
FACP supervises wiring, AC voltage and battery level.
- Silenceable or non-silenceable
- Auto-silence and silence inhibit
Three programmable Form-C relays.
24 VDC special application power outputs (resettable
and non-resettable).
A variety of optional devices can be connected to the built-
in ANN-BUS 4-conductor communication circuit. These
include: remote annunciators, a printer interface module,
LED driver module, and relay module.
•
•
Activation of a compatible smoke detector or any normally-
open fire alarm initiating device will activate audible and
visual signaling devices, illuminate an indicating LED, dis-
play message on LCD display, sound the piezo sounder at
the FACP, activate the FACP alarm relay and operate and
optional modules used to notify a remote station or initiate
an auxiliary control function.
•
•
•
Optional Class A converter module for NACs and IDCs
(model CAC-5X).
Optional transmitter module for municipal box service
and reverse polarity (model 4XTMF).
Completely field programmable at keypad
- does not require special software or extra equipment
- two password protected programming levels
80-character, backlit, high-angle, LCD display.
continued on next page
Both the Flex 505 and Flex 510 fire alarm control panel are
listed to UL® Standard 864, 9th Edition.
•
SIGNALING
FM
MEA
Reference Certificate
of Compliance
3™
i
is a trademark of Honeywell International Inc.
Approved
APPROVED
®
S1869
UL is a registered trademark of Underwriter’s Laboratories Inc.
7165-1703:0166
VMA-45894-02C
(Revision 1)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9021-60293 Rev. C page 1 of 2