E8Y
E8Y
Operation
■ FUNCTIONS
Function
Description
Pressure units
switching
Switches between mmH2O and kPa, excluding the E8Y-ꢀ-Fꢀ flow sensor.
Comparitive ON/
OFF output (two
independent
outputs
Two independent outputs can be set.
(1) Output mode (mode is automatically determined from the ON and OFF point set values.)
Hysteresis mode:
If ON point point set value > OFF point set value
For normal open:
For normal close:
Output
ON
Output
ON
OFF
OFF
0
0
Pressure value
ON set value
Pressure value
ON set value
OFF set value
OFF set value
Window mode:
If ON point set value < OFF point set value
For normal open:
For normal close:
Hysteresis width
Hysteresis width
Hysteresis width
(set value)
Hysteresis width
(set value)
(set value)
(set value)
Output
ON
Output
ON
OFF
OFF
Pressure value
OFF set value ON set value
Pressure value
ON set value
OFF set value
(2) Setting mode
ON point / OFF point: Each output can be set in the range from 0 to the rated value. Set value: 0 to rated value
Output configuration: Each output can be set as normally open (NO) or normally closed (NC).
Setting: NO <> NC
Hysteresis:
Each output can be set at 10% of the range from 0 to the rated value. (Effective in
window mode and 2-point auto-teaching mode.) Setting range: (0 to rated value) x 10%
Auto-teaching
When the auto-teaching mode is used, measured values can be input as ON point or OFF point set values
instead of key inputs. Two types of auto-teaching are available: 1-point auto-teaching, where only one single
point is set, and 2-point auto-teaching, where two points are set.
(1) 2-point auto-teaching (Hysteresis mode teaching)
This function automatically sets the ON point and OFF point for the comparative output by designating a point
with no object (TEACH 1) and a point with an object (TEACH 2) using actual objects. The outputs are made in
hysteresis mode. The hysteresis is a set value.
Hysteresis width
Output
ON
OFF
Set value
0
Pressure value
OFF ON
point point
TEACH 1
TEACH 2
The set value is the mid-point between TEACH 1 and TEACH 2.
Example: If TEACH 1 is 0.25 kPa and TEACH 2 is 0.95 kPa, the ON point set value = (0.95+0.25)/2 = 0.60
(This table continues on the next page)
5