Monitoring Relays
ꢀ
3-Phase Sequence and Phase Loss
ꢀ
Type DPA53
ꢀ
Product Description
3-Phase monitoring relay for detection of incorrect phase
sequence and phase loss. Using the front knob it can be decided
the undervoltage setpoint of the unit.
Supply range from 208 to 240VAC or 380 to 480VAC covered by
two multivoltage relays. For mounting on DIN-rail.
Housing 17.5mm wide suitable both for back and front panel
mounting.
ꢀ
Property
• Knob-adjustable undevoltage detection
• Measures its own power supply
• Power supply range: 208 to 240 and 380 to 480 VAC
• Output: 1 A SPDT relay normally energized
(±±15%
• For mounting on DIN-rail in accordance with
• ±7.1 mm DIN-rail housing (DIN 43880%
DIN/EN 10 022
• LED indication for relay and power supply ON
sequence and phase loss
• 3-phase monitoring relay for phase
• Detects all phases are present and have the correct sequence
ꢀ
Type Selection
Mounting
Output
Supply: 208 to 240 VAC
DPA 13 C M23
Supply: 380 to 480 VAC
DPA 13 C M48
DIN-rail
SPDT
ꢀ
General Specifications
Reaction time
Alarm ON delay
Alarm OFF delay
ꢀ
Input Specifications
Input
L1, L2, L3
< 100 ms
< 300 ms
Terminals L1, L2, L3
Measures its own supply
Accuracy
Temperature drift
Repeatability
(15 min warm-up time)
1000 ppm/°C
0.5% on full scale
Measuring range
M23
M48
160 to 240 VAC
320 to 480 VAC
Indication for
Power supply ON
Relay ON
Hysteresis
M23
M48
3% on full scale
4% on full scale
LED, green
LED, yellow
Environment
Degree of protection
Pollution degree
Operating temperature
@ Max. voltage, 50 Hz
@ Max. voltage, 60 Hz
Storage temperature
ꢀ
Output Specifications
Output
IP 20
2
SPDT relay, N.E.
Rated insulation voltage
Contact ratings (AgSnO2)
250 VAC
-20 to +60°C, R.H. < 95%
-20 to +50°C, R.H. < 95%
-30 to +80°C, R.H. < 95%
μ
Resistive loads
AC 1
DC 12
5 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
Housing
Dimensions
Material
Small inductive loads AC 15
DC 13
17.5 x 81 x 67.2 mm
PA66 or Noryl
Mechanical life
Electrical life
≥ 30 x 106 operations
Weight
Screw terminals
Tightening torque
Approx. 75 g
≥ 105 operations
(at 5 A, 250 V, cos ϕ = 1)
Max. 0.5 Nm
acc. to IEC 60947
Operating frequency
≤ 7200 operations/h
Dielectric strength
Product standard
Approvals
EN 60947-5-1
Dielectric voltage
≥ 2 kVAC (rms)
UL, CSA
CCC (GB14048.5)
Rated impulse withstand volt. 4 kV (1.2/50 μs)
CE Marking
L.V. Directive 2006/95/EC
EMC Directive 2004/108/EC
ꢀ
Supply Specifications
EMC
Immunity
Emissions
Power supply
Rated operational voltage
through terminals:
Overvoltage cat. III
(IEC 60664, IEC 60038)
L1, L2, L3
According to EN 61000-6-2
According to EN 61000-6-3
M23
M48
Rated operational power
208 to 240 VAC 15%,
45 to 65 Hz
380 to 480 VAC 15%,
45 to 65 Hz
M23
M48
7 VA @ 230 VAC, 50 Hz
13 VA @ 400 VAC, 50 Hz
Supplied by L1 and L3
ꢀꢁ