Dimensions DHR-C5 (in mm. 1 mm = 0.0394 inch)
25
70
60
6.80
22.28
90
4
15
7
6
78
Connections
Mechanical characteristics
· Wires up to 2 mm Æ
· General tolerance
· Primary aperture
±1 mm
DHR-C5/10
· Female connector provided (screw terminals)
Æ 32.0 mm
· Panel mounting
4 holes Æ 4.6 mm
70.0 mm & 78 mm
(see above dimensions)
DHR
· Distance between holes
For panel mounting, replace M4 screws by new one (not supplied)
with appropriate length to panel´s thickness.
Output Connector
1(Vcc) 2(NC) 3(Vout) 4(GND)
24 VDC Power
(+)
Remarks
· VOUT is positive when IP flows in the direction of the arrow.
· The return busbar and primary conductor elbow must be located
at least at 2.5 x window length more far away from the transducer
case.
(-)
10k
(-)
(+)
· The temperature of the primary busbar can not exceed 90 °C.
· Dynamic performances are the best with a primary busbar
completely filling the primary aperture.
Load
(Controller, meter etc)
· This is a standard model. For different versions (supply voltages,
different outputs, bidirectional measurements...), please
contact us.
+24VDC
OUT
Is
Ip
GND
Page 3/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
061128/14
www.lem.com