CAR3000 Series
3000 Watt 24 / 48V Front End
Features:
∎ Hot-swap N+1 Redundancy
∎ Single phase or Three phase Input
∎ Power Factor Correction
∎ Over Voltage, Over Current and Thermal Protection
∎ Visual LED Indicators
∎ 19” 3U High / 3-Bay Power Shelf
∎ International Safety Approvals
KEY MARKET SEGMENTS & APPLICATIONS
FEATURES
BENEFITS
No minimum load requirements
Modular design
Eliminates the need for preload on system backplace
Easy insertion and extraction during hot swap
One stop shopping, breadth of line
Ideal for Network Bus Applications
∎ Distributed Power
∎ Mid-end servers
∎ Blade Servers
∎ Network Equipment
∎ Test Equipment
∎ Network Storage
∎ Storage Area Networks
Single phase or three phase inputs
Constant current characteristics
SPECIFICATIONS
Input Voltage Range
Input Current
CAR3010K1
Single Phase Input / 180-264 VAC / 47-63 Hz
CAR3010L1
CAR3030K1
Three Phase Input / 180-264 VAC / 47-63 Hz
11A per phase max.
CAR3030L1
19Amax
50Amax
Inrush Current
50A max (per phase)
Input Fuse
Power Factor
Single Fuse 25A 3AG
0.99
Single Fuse per Phase 15A 3AG
0.95
Efficiency
90% Typical @ 230 VAC
90% Typical @ 230 VAC
Output Voltage & Current
Adjust Range (Trim Pot)
Over Voltage Protection
+24 VDC @ 125A
21.6~26.4
29.5~30.5 VDC
+48 VDC @ 62.5A
43.2~52.8
58.5~59.5 VDC
+24 VDC @ 125A
21.6~26.4
29.5~30.5 VDC
+48 VDC @ 62.5A
43.2~52.8
58.5~59.5 VDC
OVP Protection Type
Recycle AC Input to Reset
Standby Voltage
5VSB @ 500mA
Line Regulation
0.5% using remote sense (5% on Stand-by Voltage)
Load Regulation
0.5% using remote sense (5% on Stand-by Voltage)
Output Ripple & Noise
Transient Response
Start-up Time
<1% (pk-pk)
3% max deviation 0.50ms recovery time for a 25% load change
2 seconds
Hold-up Time
>20ms at low line
1% at turn ON/OFF
0.02% per °C
Overshoot / Undershoot
Temperature Coefficient
Remote ON/OFF
Power Fail Signal
Over Current Protection
Logic 1 (TTL High) or open enables unit (ON), Logic 0 (TTL Low) or short shuts unit down (OFF)
Signal goes low (TTL Low) 2ms before loss output regulation
110-140% V1, 5VSB < 2.5A. Automatic recovery.
Over Temperature Protection Automatic shutdown with auto recovery. Thermal shutdown point @ 95°C
MTBF
300,000 hrs per Bellcore standard
Output Power Good
LED Indicators
Operating Temperature
Cooling
TTL High = Power Good, TTL Low = Output out of limits
DC Good: Green LED; Temperature OK: Green LED and AC Good: Amber LED
0°C to 50°C at rated output power. Supply derates linearly from 50°C to 65°C at 2.2% per °C
Self contained ball bearing fan
EMI/EMC
Dimensions
Weight
Meets EN61000-3-2, -3 CISPR22 and FCC Part 15 Class A, Bellcore GR-1089-CORE
12.12 x 5.00 x 5.00” / 333.2 x 127 x 127mm (handle extends additional 1.00” / 25.4mm from faceplate)
11.5 pounds / 5.23 kg
Safety Approvals
UL1950, CSA 22.2 No. 650, TUV EN0950 & CE Mark
www.lineagepower.com/oem
rev 100506
Lineage Power
Lineage Power
Lineage Power (China)
3000 Skyline Dr.
Mesquite, TX 75149
Phone: (972) 284-2000
2841 Dow Avenue
Tustin, CA 92780 USA
Phone: (714) 544-6665
1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Shanghai, 201401 China
Phone: 021 6710 8910