Limit Alarms (rotary switch adj.) AL-UNIT

ALDY-12-B/Q 数据手册

 浏览型号ALDY-12-B/Q的Datasheet PDF文件第2页浏览型号ALDY-12-B/Q的Datasheet PDF文件第3页浏览型号ALDY-12-B/Q的Datasheet PDF文件第4页 
MODEL: ALDY  
Limit Alarms (rotary switch adj.) AL-UNIT  
[2] SETPOINT 2 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
TWO-WIRE TRANSMITTER ALARM  
Functions & Features  
• Powering a 4 – 20 mA DC current loop  
• Providing SPDT relay outputs at preset current levels  
• Shortcircuit protection  
[3] POWER INPUT  
AC Power  
• Applicable to smart transmitters  
• Dual (Hi/Lo) trip  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
• Energized or de-energized coil at a tripped condition  
selectable  
• Rotary switch setpoint adjustments  
• Enclosed relays  
• Relays can be powered 110 V DC  
• High-density mounting  
DC Power  
Typical Applications  
• Annunciator  
S: 12 V DC  
R: 24 V DC  
• Various alarm applications  
V: 48 V DC  
P: 110 V DC  
50  
(1.97)  
[4] OPTIONS  
blank: none  
80  
(3.15)  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
132  
(5.20)  
mm (inch)  
/C02: Polyurethane coating  
/C03: Rubber coating  
MODEL: ALDY–[1][2]–[3][4]  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
ORDERING INFORMATION  
• Code number: ALDY-[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. ALDY-11-B/Q)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output 1 to output 2 to power  
Setpoint adjustments: 10-position rotary switches (front); 0  
– 99 % independently; 1 % increments  
Hysteresis (deadband): 0.7 – 2.5 %  
INPUT  
Current  
4 – 20 mA DC (Input resistance 250 Ω)  
Front LEDs: Red LED turns on when the coil is energized.  
Power ON timer: Relays de-energized for approx. 2 seconds  
after power is turned on.  
[1] SETPOINT 1 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
SUPPLY OUTPUT  
Output voltage: 24 – 28 V DC with no load  
Current rating: ≤ 22 mA DC  
ALDY SPECIFICATIONS  
ES-2726 Rev.2 Page 1/4  
http://www.m-system.co.jp/  

与ALDY-12-B/Q相关器件

型号 品牌 获取价格 描述 数据表
ALDY-12-C MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT
ALDY-12-C/Q MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT
ALDY-12-D MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT
ALDY-12-D/Q MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT
ALDY-12-F MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT
ALDY-12-F/Q MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT
ALDY-12-G MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT
ALDY-12-G/Q MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT
ALDY-12-J MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT
ALDY-12-J/Q MSYSTEM

获取价格

Limit Alarms (rotary switch adj.) AL-UNIT