Magnetic and Hydraulic-Magnetic Circuit Breaker 8345-...
Ordering information for EN 60934 and UL 1077
Type No.
8345
Ordering information for auxiliary contact module
Mounting
Type number
X8345
B flange mounting, with rectangular aperture with mounting nut 6-32UNC
C flange mounting, with rectangular aperture with mounting nut M3
F flange mounting, with round aperture with mounting nut M3
Configuration
0 without barrier
1 with small barrier
2 with large barrier (requested for multipole AC applications)
Number of poles
1 single pole protected
2 two pole protected
3 three pole protected
Module
S auxiliary contact module
Auxiliary contacts
01 in all poles
02 in pole 1 only
Auxiliary contact version
K
auxiliary contacts (symmetrical terminals)
Auxiliary contact function
W1 1 changeover
1
Terminal design
02 microswitch with blade terminals
DIN 46244-A2.8-0.5
4 four pole protected
Actuator configuration
A
B
Z
all poles with standard toggle
reduced number of standard toggles
without actuator
M
mounted to base unit
X8345
-
S 01 K W1 02 M ordering example
Terminal design
P blade terminals ≤ 35 A
R round connectors 6 mm
U stud terminals M6 ≤ 125 A
V stud terminals 1/4-20UNC-3A ≤ 125 A
W laminated round terminals ≤ 125 A
Terminal hardware
0 without
3 with washer and nut
Characteristic curve *)
Characteristic curve, instantaneous:
F1 DC
Approvals
Authority Standard Rated voltage Current ratings
AC 240/415 V 0.016 A…80 A
VDE
IEC / EN
60934
AC 240 V
DC 80 V
0.016 A…80 A
0.02 A…125 A
AC 277/480 V 0.02 A…70 A
UL
UL 1077
C22.2 No
235
AC 277 V
DC 80 V
0.02 A…70 A
0.02 A…125 A
F2 AC 60/50 Hz
Short delay:
K1 DC
K2 AC
Medium delay:
M1 DC
AC 120/240 V 0.05 A…80 A (2 pole)
UL
UL 489
C22.2
No 5
AC 240 V
AC 120 V
DC 80 V
0.05 A…20 A (1 pole)
0.05 A…80 A (1 pole)
0.05 A…125 A (1+2 pole)
CSA
CQC
M2 AC 60/50 Hz
Long delay:
T1 DC
T2 AC 60/50 Hz
AC 240/415 V 0.02 A…80 A (3 pole)
GB
17701
AC 240 V
DC 80 V
DC 110 V
0.02 A…80 A (1 + 2 pole)
0.02 A…125 A (1 + 2 pole)
0.05 A…125 A (1 + 2 pole)
Version
D
standard
Colour configuration
B1 black actuator
Marking
front plate
actuator base
ON-OFF
B1 without
B2 IN
ON-OFF
Rated voltage
B
AC or ≤ 80 V DC
Current ratings
0.05...125 A
higher current ratings
upon request
8345 - C 0 1 A - U 3 M1 - D B1 B1 B - 60 A ordering example
Remote trip coil available to special order.
*) Other characteristic curves upon request (e.g. pulse delayed, for high
inrush currents or capacitive loads)
Note:
Move actuator of multipole devices slowly and smoothly into
ON position to ensure reliable latch-on behaviour of all poles.
2
www.e-t-a.de
1651