Motor and Pump Protection Relays
77C Series
Specifications
Functional Characteristics
Frequency
50/60 Hz
TC- Overcurrent Trip Class
(77C, 777 non-Plus Series units)
5, 10, 15, 20, 30 (J prefix enables jam protection feature)
Output Characteristics
Output Contact Rating (SPDT - Form C)
Pilot duty rating
480 VA @ 240 V ac, B300
10 A @ 240 V ac
470 VA @ 600 V ac, B600
General purpose
Pilot duty rating for HVR models
General Characteristics
Ambient Temperature Range
Operating
Storage
-20 °C to 70 °C (-4 °F to 158 °F)
-40 °C to 80 °C (-40 °F to 176 °F)
Accuracy
Voltage
1 ꢀ
Current
3 ꢀ(ꢁ100 amps direct)
15 ꢀ
GF Current
Timing
(77C, 777 non-Plus Series units)
5 ꢀ +1 second
Repeatability
Voltage
0.5 ꢀ of nominal voltage
Current
1 ꢀ (ꢁ100 amps direct)
Maximum Input Power
Pollution Degree
Class of Protection
Relative Humidity
Terminal Torque
10 W
3
IP20
10-95 ꢀ, non-condensing per IEC 68-2-3
7 in.-lbs.
Standards Passed
Electrostatic Discharge (ESD)
IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
Radio Frequency Immunity (RFI)
Conducted
Radiated
IEC 61000-4-6, Level 3 10 V/m
IEC 61000-4-3, Level 3 10 V/m
Fast Transient Burst
Short Circuit
Surge
IEC 61000-4-4, Level 3, 3.5 kV input power
100 kA
IEC
61000-4-5, Level 3, 2 kV line-to-line; Level 4, 4 kV line-to-ground
C62.41 Surge and Ring Wave Compliance to a level of 6 kV line-to-line
Meets UL 508 (2 x rated V +1000V for 1 minute)
IEC 68-2-6, 10-55 Hz, 1 mm peak-to-peak, 2 hours, 3 axis
IEC 68-2-27, 30 g, 3 axis, 11 ms duration, half-sine pulse
ANSI/IEEE
Hi-potential Test
Vibration
Shock
Maximum Conductor Size
(with insulation) through 77C
0.65”
Dimensions
Weight
H 77.47 mm (3.05”); W 97.79 mm (3.85”); D 128.27 mm (5.05”)
1.56 lbs. (24.96 oz., 707.6 g)
Mounting Method
Surface mount (4 - #8 screws) or DIN rail mount
Certification & Compliance
UL
UL 508, UL 1053 (File #E68520)
IEC 60947-1, IEC 60947-5-1
C22.2
CE
CSA
Littelfuse.com/77C
©2022 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 09/30/2022