4页 117K
描述
Current Transformer, 1000:5A, 1% Accuracy Class, ROHS COMPLIANT

7020-01044-0 技术参数

是否无铅: 不含铅是否Rohs认证: 符合
生命周期:Obsolete包装说明:ROHS COMPLIANT
Reach Compliance Code:compliantECCN代码:EAR99
HTS代码:8504.31.40.35风险等级:8.61
精度等级:1认证:UL
额定电流 (Ip:Is):1000:5 A直径:114.3 mm
高度:28.7 mm安装特点:THROUGH HOLE MOUNTED
最大工作频率:0.4 kHz最小工作频率:0.05 kHz
物理尺寸:D114.3XH28.7 (mm)初级类型:BAR PRIMARY
最大次级负载:10 VA表面贴装:NO
变压器类型:CURRENT TRANSFORMER窗口尺寸:76.2 m
Base Number Matches:1

7020-01044-0 数据手册

 浏览型号7020-01044-0的Datasheet PDF文件第2页浏览型号7020-01044-0的Datasheet PDF文件第3页浏览型号7020-01044-0的Datasheet PDF文件第4页 
DMS Accessories  
s
5 Amp AC Current Transformers  
These commercial grade, UL & CSA recognized, “donut style” AC current-transformers  
(CTs) provide an isolated 0-5A output that can be used with Murata Power Solutions’ ACA5  
Series of digital ammeters. Installation is straightforward: simply pass the load-carrying  
conductor through the 5A CT’s primary window, and then route its secondary’s leads  
through the ACA5-ammeter’s built-in, low-burden, toroid sensor.  
All models feature rugged, fully insulated construction, allowing continuous operation  
with primary voltages up to 600Vac, at line frequencies from 50 to 400Hz. Fourteen models  
are available to enable accurate measurements from 50A through 2000A. When combined  
with Murata Power Solutions’ ACA5 Series ammeters, secondary lead-extensions may be  
used for those applications where the CT cannot be installed in the immediate vicinity of  
the ammeter.  
GENERAL SPECIFICATIONS (ALL MODELS)  
Insulation Class  
Frequency Range  
Supplied Secondary  
Max. Secondary Lead  
Rated Accuracy  
Burden  
600V, 10kV BIL full wave  
50-400Hz  
See Table 1  
UL FIle No.  
CSA File No.  
TECHNICAL NOTES  
Weight  
IMPORTANT! To ensure safe and reliable operation, Current Transformers and asso-  
ciated equipment must be installed and serviced by qualified technical personnel.  
Never open the CT’s secondary connections while the primary is energized. Open  
CT secondary wiring can generate potentially lethal voltages when the primary cir-  
cuit is energized. Contact Murata Power Solutions if you have any doubts regarding  
the installation or operation of any of our ac-mains measurement instruments and  
accessories.  
Basic Lightning Impulse Insulation Level (BIL): The insulation  
strength referenced to the crest value of an impulse voltage-  
waveform which rises to a crest value in 1.2 microseconds, then  
drops to ½ the crest value in 50 microseconds.  
1. CT Precautions: In normal operation, a 5A current transformer’s secondary circuit oper-  
ates at a relatively low voltage due to its closed-loop, low burden configuration (essentially  
zero Ohms when used with Murata Power Solutions’ ACA5 series ammeters). However,  
any CT can generate potentially lethal voltages if its output current is suddenly interrupted.  
For example, loose secondary connections can produce a condition referred to as “induc-  
tive kick.” Inductive kick can generate extremely high voltages across the open secondary  
connections.  
AC POWER  
SUPPLY  
ACA5-20PC-X-ACX  
A
B
TB1  
Therefore, all connections made to a CT’s secondary leads must only be performed with  
zero current flowing in the primary circuit. Never operate a CT with its secondary circuit  
open and current flowing in the primary.  
TO AC LOAD  
L1  
5A CURRENT  
TRANSFORMER  
2. CT Connections and Grounding: Some applications require connecting one of the CT’s  
5A output terminals to earth/chassis ground. In the USA, consult the latest revision of the  
National Electrical Code for more information.  
(see technical notes)  
0-5A  
OUTPUT  
After all mechanical assembly is completed, pass the 5A secondary leads through the  
ACA5 ammeter’s built-in toroid, then connect the two leads together as shown in Figure  
1. For this connection, and for connections involving lead extensions, pressure-style  
connectors (commonly called “wire nuts”) are acceptable as long as they are rated for the  
currents and voltages involved.  
Figure 1.Typical Connections  
3. Installation: CT’s must be installed in a manner that ensures no excessive stresses are  
applied to the primary conductor that passes through the CT or to the secondary circuit  
and its associated instruments. Use plastic tie-wraps and/or other suitable non-conductive  
restraining devices to secure the CT.  
For full details go to  
www.murata-ps.com/rohs  
www.murata-ps.com/support  
MPM_DMS-CT.B03 Page 1 of 4  

与7020-01044-0相关器件

型号 品牌 获取价格 描述 数据表
7020-01045-0 MURATA

获取价格

Current Transformer, 1500:5A, 1% Accuracy Class, ROHS COMPLIANT
702001A13 MOLEX

获取价格

Circular Connector
702001B01F060 MOLEX

获取价格

Circular Connector, Plug
702001B01F120 MOLEX

获取价格

Circular Connector, Plug
702001B01F200 MOLEX

获取价格

Circular Connector, Plug
702001D02F060 MOLEX

获取价格

Circular Connector,
702001D02F120 MOLEX

获取价格

Circular Connector, Plug
702002B01 MOLEX

获取价格

Circular Connector
702002B01F060 MOLEX

获取价格

Circular Connector, Plug
702002B01F120 MOLEX

获取价格

Circular Connector, Plug