26 pF/ft
47 pF/ft
Inductance
Nominal Inductance
0.197 µH/ft
Impedance
Nominal Characteristic Impedance
71 Ohm
Current
Max. Recommended Current [A]
30 Amps per conductor @ 30°C (per NEC)
Voltage
Description
UL Voltage Rating
Voltage Rating [V]
CSA AWM I/II A/B 1000 V RMS (Flexible Motor Supply Cable) 1000 V RMS
600 V RMS (Type TC)
Temperature Range
UL Temp Rating:
Wet Temp Range:
Dry Temp Range:
90°C Dry, 90°C Wet
-40°C To +90 °C
-40°C To +90 °C
Mechanical Characteristics
Bulk Cable Weight:
250 lbs/1000ft
Max Recommended Pulling Tension: 336 lbs
Min Bend Radius/Minor Axis:
6.3 in
Standards
NEC/(UL) Specification:
CPR Euroclass:
TC-ER, Unlisted Singles, WTTC
Fca
Applicable Environmental and Other Programs
EU Directive Compliance:
EU CE Mark:
EU Directive 2003/11/EC (BFR)
Yes
Yes
Yes
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Suitability
Suitability - Burial:
Yes
Yes
Yes
Yes
Yes
Suitability - Indoor:
Suitability - Oil Resistance:
Suitability - Outdoor:
Suitability - Sunlight Resistance:
Flammability, LS0H, Toxicity Testing
UL Flammability:
CSA Flammability:
IEEE Flammability:
UL voltage rating:
UL1685 UL Loading
FT4
1202
1000 V RMS (Flexible Motor Supply Cable)
Part Number
Variants
Item #
Color
UPC
Length Footnote
29502X 0105000 Black 612825136842 5,000 ft C Z
Footnote:
Footnote:
C - CRATE REEL PUT-UP.
Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.
History