Limit and Enclosed Switches
CX Series
Weather-Sealed Explosion-Proof Switches
FEATURES
ɀ Sealing - applicable portions of NEMA 1,
3, 4, 4X, 6, 6P, 7, 9, and 13
CX switches are built especially for outdoor NEMA standards: 1, 3, 4, 4X, 6, 6P, 7, 9 and
use in hazardous atmospheres. These en- 13.
closures are constructed to withstand the UL listed: Class I, Div. 1, Groups B (14CX,
pressure of an internal explosion. Flame 16CX, 24CX, 26CX, 36CX, and84CXonly), C
paths cool the exploded gases to a point and D; and Class II, Div. 1, Groups E, F and
less than the lowest safe operating temper- G. CSA certified: Class I, Div. 1, Groups B
ɀ Watertight and dusttight for outdoor use
ɀ 4-20 mA analog output available
ɀ UL Listed, file #E14274
ɀ Analog UL file #E68247
ature of the surrounding gas.
(14CX, 16CX, 24CX, 26CX, 36CX and 84CX
only), CandD;andClassII, GroupsE, Fand
G.
ɀ CSA Certified, file #LR57324
ɀ Rugged cast aluminum housing
ɀ Pretravel, overtravel, and actuating
sequence can be field adjusted without
tools (all basics individually)
O-ring seals make the enclosure weather-
proofbutareoutsideofrequiredflamepaths
so explosion proof requirements are main-
tained.
For rapid response – off the shelf service,
all bold face listings are normally stocked
items.
ɀ Rotary types convert in seconds to
clockwise, counterclockwise, or both-
way operation
Analog output: either resistive or 4-20 mA is
available.
Operating temperature range is –25° to
+85°C (–13° to 185°F).
ROTARY ACTUATED SWITCHES
ORDER GUIDE
As factory assembled, all basic switches
operateonclockwiseandcounterclockwise
rotation. Actuating mechanism can be field
adjusted for CW or CCW operation only. No
tools are required.
Catalog Listings
Shaft Restoring
Force To Center
Housing
Size
Basic
Switch(es)
Electrical
Ratings
Short housing
1
2
2
Description
15 amp. SPDT.
With
W/O
11CX1
Short
Short
Standard
Standard
BZ(1)
BZ(2)
BZ(3)
BZ(4)
A
A
A
A
11CX2
11CX12
21CX13
21CX14
21CX4
20 amp. SPDT.
12CX1
12CX2
Short
Short
BA(1)
BA(2)
B
B
12CX12
22CX4
Standard
BA(4)
B
Also UL listed for Class I.
14CX1
14CX11
24CX12
24CX13
Short
Standard
Standard
DT(1)
DT(2)
DT(3)
C
C
C
Group B (hydrogen atmospheres). 24CX2
10 amp. DPDT.
Standard housing
Also UL listed for
Class I, Group B
(hydrogen atmospheres).
1 amp, SPDT.
16CX2
26CX4
16CX1
16CX12
26CX14
16CX11
Short
Standard
Short
HS(2)
HS(4)
HS(1)
D
D
D
Actuators are not included with switch. Or-
der them separately.
Analog position sensing.*
Current output (4-20 mA).
—
—
18CX10
281CX12
284CX12
Short
Standard
Standard
None
BZ(2)
DT(2)
—
A
ROTARY LEVERS
Catalog
C
1 amp, SPDT with
gold contacts.
1172CX2 1172CX12
Short
BZ(2)
F
Lever Type
Listing
1.5 in. lever, no roller
.75 in. roller, front
.75 in. roller, back
LSZ51
LSZ51A
LSZ51C
1.5-3.5 in. adjustable lever
.75 in. roller
* Where noted, BZ basic switches are15 amp, SPDT; DT basic switchs are10 amp DPDT. Refer to next page for
analog position sensing specifications.
LSZ52C
LSZ52J
LSZ52K
1.0 in. roller
1
MOUNTING HOLES
Add the letter A to listings with side mount-
ing holes tapped 5/16-18(8).
Basic switches operate nearly simultane-
ously in multiple switch devices.
Shafts of devices without shaft restoring
force can be rotated through 360°.
1.5 in. roller
1.5 in. yoke roller
.75 in. rollers, back
.75 in. rollers, each side
2
LSZ53S
LSZ53E
Example: 11CX2A
5 in. rod lever
Hub only
LSZ54M
LSZ54
Add the letter B to listings with thru mount- Basic switches will be in operated mode
ing holes tapped 3/8-24(4).
through two 105° sections.
1.5 in. offset lever, no roller
.75 in. roller, back
.75 in. roller, front
LSZ55
LSZ55A
LSZ55C
Example: 11CX2B.
Eight side mounting holes can be tapped
5/16⍯-18.
Rollers are nylon. Non-sparking rollers must
be used in hazardous locations.