7
0RQB-X0S11x
1. The Power Good signal is a non-latching open-collector output that is Low during normal operation and is pulled High when
any of the following conditions occur:
•
•
•
•
Over-Temperature
Over-Current
Vout is outside of the DC Output Band while Vin is within the Vin Operating Range
Vin is within the Vin Operating Range but the unit is not operating (to determine if 1 Unit used in a parallel configuration
is not operating)
•
Vin is outside of the Vin Operating Range
2. The Power Good signal is referenced to Vout(-).
PARAMETER
DESCRIPTION
MIN
8.6
12.8
42.5
59
-
TYP
MAX
9.0
13.2
45
UNIT
Output Voltage High (trigger limits)
Output Voltage High (trigger limits)
Input Voltage Low (trigger limits) Rising
Input Voltage High (trigger limits) Rising
Hysteresis
-
-
-
-
1
-
-
-
-
V
V
PG signal indicates good when Vin is within
operating range and indicates bad ~20ms before
unit is shut-down due to OV
V
62
V
-
V
High State Voltage
0
5.5
10
V
High State Leakage Current (into Pin)
Low State Voltage
0
µA
V
0
0.8
5
Low State Current (into Pin)
0
mA
Power Good Signal
De-assert Response Time
Power Good Signal
Duration between the fault occurring and the
Power-Good Signal de-asserting
Duration between unit powering up with no faults
and the Power Good Signal asserting
Duration the Power-Good signal stays de-asserted
if a transient fault occurs
0
0
-
-
3
3
ms
ms
ms
oC
Assert Response Time
Power Good Signal Duration
200
600
For OT Warning, the PG signal will toggle as an
impulse wave.
Over Temperature Warning
120
OT Warning PG signal frequency
OT Warning PG signal duty cycle
70
-
110
kHZ
%
47.5
50
52.5
Testing setup:
is
ic
Ls
Vin+
+
+
Cs
Cin
Vin-
Notes and values in testing.
Ls: Simulated Source Impedance (10uH).
Cs: Offset possible source Impedance (100μF, ESR<0.2Ω@ 100kHz, 20C ).
Cin: Electrolytic capacitor, should be as closed as possible to the power module to swallow ic ripple current and
help with stability. Recommendation: 100μF, ESR<0.2Ω@ 100kHz, 20C.
North America
Asia-Pacific
Europe, Middle East
+1 408 785 5200
+86 755 298 85888
+353 61 225 977
© 2017 Bel Power Solutions & Protection
Rev. AD1